Assessment Year | 2004 |
---|---|
Principal Product | Custom Bags |
NAICS | 314910: Textile Bag and Canvas Mills |
SIC | 2393: Textile Bags |
Sales Range | $10 M to 50M |
# of Employees | 110 |
Plant Area |
49,000
ft2
|
Annual Production | 20,000,000
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $79,614 | 1,582,272 |
kWh
|
$0.050 |
Electricity Demand | $38,139 | 5,443 |
kW-mo/yr
|
$7.01 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,625 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,546 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $8,836 | $43,080 |
$4,931
98,032
kWh
|
$3,905
-
kW-mo/yr
|
|
02 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $8,144 | $35,305 |
$5,494
109,225
kWh
|
$2,650
-
kW-mo/yr
|
|
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,386 | $6,346 |
$2,159
42,923
kWh
|
$1,227
-
kW-mo/yr
|
|
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,153 | $9,850 |
$2,153
42,805
kWh
|
- | |
05 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $1,720 | $6,500 |
$1,720
34,207
kWh
|
- | |
06 | 2.7243: Improve air circulation with destratification fans / other methods | $1,297 | $4,020 |
$659
13,104
kWh
|
$638
-
kW-mo/yr
|
|
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $915 | $100 |
$508
10,098
kWh
|
$407
-
kW-mo/yr
|
|
08 | 2.7135: Install occupancy sensors | $411 | $1,125 |
$411
8,163
kWh
|
- | |
09 | 2.4221: Install compressor air intakes in coolest locations | $132 | $300 |
$80
1,594
kWh
|
$52
-
kW-mo/yr
|
|
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,631 | $76,467 |
$4,224
83,971
kWh
|
$3,407
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $34,625 | $183,093 |
$22,339
444,122
kWh
|
$12,286
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $8,546 | $76,567 |
$4,732
94,069
kWh
|
$3,814
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs