Assessment Year 2003
Principal Product Aerosol Cans
NAICS 332431: Metal Can Manufacturing
SIC 3411: Metal Cans
Sales Range $50
M
to 100
M
# of Employees 220
Plant Area 147,398
ft2
Annual Production 400,000,000
pieces
Production Hrs. Annual 7,488
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $481,648 9,198,000
kWh
Electricity Demand $199,662 16,597
kW-mo/yr
Natural Gas $116,889 15,478
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $104,496 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $57,363

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.4226: Use / purchase optimum sized compressor $55,709 $87,769 $30,041
573,304
kWh
$5,668
-
kW-mo/yr
- $20,000
02 2.7442: Keep doors and windows shut when not on use $13,957 - - - $13,957
-
MMBtu
-
03 2.3191: Use demand controller or load shedder $9,985 $5,000 - $9,985
-
kW-mo/yr
- -
04 2.4221: Install compressor air intakes in coolest locations $8,304 $4,000 $5,796
110,609
kWh
$2,508
-
kW-mo/yr
- -
05 2.2511: Insulate bare equipment $5,770 $985 - - $5,770
-
MMBtu
-
06 2.4314: Use synthetic lubricant $5,893 $1,000 $1,586
30,269
kWh
$4,307
-
kW-mo/yr
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $3,224 $17,804 $2,358
45,003
kWh
$866
-
kW-mo/yr
- -
08 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,654 - $1,229
23,461
kWh
$425
-
kW-mo/yr
- -
TOTAL RECOMMENDED $104,496 $116,558 $41,010
782,646
kWh
$23,759
-
kW-mo/yr
$19,727
-
MMBtu
$20,000
TOTAL IMPLEMENTED $57,363 $87,769 $31,270
596,765
kWh
$6,093
-
kW-mo/yr
- $20,000
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs