| Assessment Year | 2022 |
|---|---|
| Principal Product | Metal Food Cans and Metal Lids |
| NAICS | 332431: Metal Can Manufacturing |
| SIC | 3411: Metal Cans |
| Sales Range | $50 M to 100M |
| # of Employees | 150 |
| Plant Area |
62,000
ft2
|
| Annual Production | 2,400,000,000
pieces
|
| Production Hrs. Annual | 8,160
hrs
|
| Location (State) | Wisconsin |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $551,004 | 8,797,700 |
kWh
|
$0.063 | |
| Electricity Demand | $186,979 | 16,009 |
kW-mo/yr
|
$11.68 | |
| Electricity Fees | $21,585 | - |
|
- | |
| Natural Gas | $48,826 | 4,332 |
MMBtu
|
$11.27 | |
| Waste Disposal Costs | |||||
| Water Usage | $5,295 | 217 |
Tgal
|
$24.40 | |
| TOTAL YEARLY COSTS | $813,689 | ||||
| RECOMMENDED SAVINGS* | $51,321 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $29,905 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $28,565 | $28,700 |
$23,112
369,188
kWh
|
$5,453
-
kW-mo/yr
|
- | |
| 02 | 2.7231: Use radiant heater for spot heating | $10,088 | $23,040 | - | - |
$10,088
-
MMBtu
|
|
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,563 | $4,800 | - | - |
$7,563
-
MMBtu
|
|
| 04 | 2.7444: Close holes and openings in building such as broken windows | $3,178 | $2,050 | - | - |
$3,178
-
MMBtu
|
|
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $587 | $243 |
$484
7,735
kWh
|
$103
-
kW-mo/yr
|
- | |
| 06 | 2.7221: Lower temperature during the winter season and vice-versa | $471 | - |
$388
6,203
kWh
|
$83
-
kW-mo/yr
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $443 | $1,250 |
$366
5,848
kWh
|
$77
-
kW-mo/yr
|
- | |
| 08 | 2.7229: Air condition only space necessary | $426 | - |
$244
3,894
kWh
|
$182
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $51,321 | $60,083 |
$24,594
392,868
kWh
|
$5,898
-
kW-mo/yr
|
$20,829
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $29,905 | $29,950 |
$24,110
385,133
kWh
|
$5,796
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs