Assessment Year | 1991 |
---|---|
Principal Product | CENTRIFUGAL PUMPS |
NAICS |
n/a
|
SIC | 3561: Pumps and Pumping Equipment |
Sales Range | $50 M to 100M |
# of Employees | 300 |
Plant Area |
n/a
|
Annual Production | 0
units
|
Production Hrs. Annual | 4,190
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $262,587 | 4,654,748 |
kWh
|
$0.056 |
Natural Gas | $45,353 | 15,663 |
MMBtu
|
$2.90 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $37,775 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $12,017 | $3,600 |
$12,017
213,072
kWh
|
- | |
02 | 2.7261: Install timers and/or thermostats | $8,091 | $9,690 | - |
$8,091
-
MMBtu
|
|
03 | 2.7261: Install timers and/or thermostats | $774 | $1,140 |
$264
4,689
kWh
|
$510
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,753 | $500 |
$7,753
137,456
kWh
|
- | |
05 | 2.3512: De-energize excess transformer capacity | $4,942 | $100,000 |
$4,942
87,632
kWh
|
- | |
06 | 2.6232: Install set-back timers | $2,678 | $550 |
$2,678
47,479
kWh
|
- | |
07 | 2.7314: Reduce ventilation air | $1,195 | $200 |
$397
7,034
kWh
|
$798
-
MMBtu
|
|
08 | 2.7221: Lower temperature during the winter season and vice-versa | $325 | - | - |
$325
-
MMBtu
|
|
TOTAL RECOMMENDED | $37,775 | $115,680 |
$28,051
497,362
kWh
|
$9,724
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs