Assessment Year | 1984 |
---|---|
Principal Product | CUSTOM KITCHEN CABINETS |
NAICS |
n/a
|
SIC | 2434: Wood Kitchen Cabinets |
Sales Range | $5 M to 10M |
# of Employees | 165 |
Plant Area |
n/a
|
Annual Production | 1,850
pieces
|
Production Hrs. Annual | 2,300
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $71,967 | 863,130 |
kWh
|
$0.083 |
Natural Gas | $13,650 | 2,665 |
MMBtu
|
$5.12 |
Fuel Oil #1 | $3,150 | 402 |
MMBtu
|
$7.84 |
Other Energy | $18,846 | 2,194 |
MMBtu
|
$8.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,596 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,632 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #1 Savings | Other Energy Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,142 | $6,807 |
$8,142
97,597
kWh
|
- | - | - | - | |
02 | 2.4312: Improve lubrication practices | $3,765 | $800 |
$3,765
45,135
kWh
|
- | - | - | - | |
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $3,978 | $3,155 | - |
$3,978
-
MMBtu
|
- | - | - | |
04 | 2.3191: Use demand controller or load shedder | $1,907 | $1,150 |
$1,907
-
kWh
|
- | - | - | - | |
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $903 | - | - |
$1,853
-
MMBtu
|
- | - | $(-950.0) | |
06 | 2.1123: Install automatic stack damper | $840 | $1,625 | - |
$840
-
MMBtu
|
- | - | - | |
07 | 2.6214: Shut off pilots in standby equipment | $238 | - | - |
$338
-
MMBtu
|
- | - | $(-100.0) | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,443 | $85 |
$1,443
17,292
kWh
|
- | - | - | - | |
09 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $1,418 | $1,110 |
$1,418
16,999
kWh
|
- | - | - | - | |
10 | 2.4221: Install compressor air intakes in coolest locations | $171 | $50 |
$171
2,052
kWh
|
- | - | - | - | |
11 | 2.7314: Reduce ventilation air | $808 | - |
$269
3,224
kWh
|
$1,039
-
MMBtu
|
- | - | $(-500.0) | |
12 | 2.6121: Reduce hot water temperature to the minimum required | $954 | - |
$954
11,430
kWh
|
- | - | - | - | |
13 | 2.4322: Use or replace with energy efficient substitutes | $662 | - | - | - |
$95
-
MMBtu
|
$567
-
MMBtu
|
- | |
14 | 2.4322: Use or replace with energy efficient substitutes | $367 | $800 |
$367
4,396
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $25,596 | $15,582 |
$18,436
198,125
kWh
|
$8,048
-
MMBtu
|
$95
-
MMBtu
|
$567
-
MMBtu
|
$(-1,550.0) | ||
TOTAL IMPLEMENTED | $21,632 | $12,757 |
$16,089
192,849
kWh
|
$5,831
-
MMBtu
|
$95
-
MMBtu
|
$567
-
MMBtu
|
$(-950.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Fuel Oil #1 Savings | Other Energy Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs