ITAC Assessment: KU0116
ITAC logo
ITAC Assessment: KU0116
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1984
Principal Product JEANS,JACKETS
NAICS
n/a
SIC 2325: Men's and Boys' Separate Trousers and Slacks
Sales Range $10
M
to 50
M
# of Employees 430
Plant Area
n/a
Annual Production 1,500,000
pieces
Production Hrs. Annual 5,712
hrs
Location (State) Kansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $113,581 1,772,861
kWh
Natural Gas $63,404 12,247
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $39,375 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $5,151

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Other Energy Savings Administrative Changes Savings
01 3.6122: Install solid waste incinerator for heat $22,384 $41,760 - $27,739
-
MMBtu
$(-5,355.0)
-
MMBtu
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $4,279 $4,658 $4,279
66,823
kWh
- - -
03 2.6212: Turn off equipment during breaks, reduce operating time $1,138 - - $1,538
-
MMBtu
- $(-400.0)
04 2.7442: Keep doors and windows shut when not on use $1,182 $100 $94
1,465
kWh
$1,088
-
MMBtu
- -
05 2.2437: Recover waste heat from equipment $3,118 $525 - $3,118
-
MMBtu
- -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,515 $230 $2,515
39,273
kWh
- - -
07 2.4231: Reduce the pressure of compressed air to the minimum required $848 - $848
13,189
kWh
- - -
08 2.4221: Install compressor air intakes in coolest locations $370 $410 $370
5,862
kWh
- - -
09 2.7228: Avoid introducing hot, humid, or dirty air into hvac system $2,065 $3,200 $2,065
32,239
kWh
- - -
10 2.1123: Install automatic stack damper $896 $2,095 - $896
-
MMBtu
- -
11 2.2511: Insulate bare equipment $316 $60 - $316
-
MMBtu
- -
12 2.2122: Install / repair insulation on condensate lines $264 $160 - $264
-
MMBtu
- -
TOTAL RECOMMENDED $39,375 $53,198 $10,171
158,851
kWh
$34,959
-
MMBtu
$(-5,355.0)
-
MMBtu
$(-400.0)
TOTAL IMPLEMENTED $5,151 $390 $2,609
40,738
kWh
$2,942
-
MMBtu
- $(-400.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Other Energy Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs