| Assessment Year | 1995 |
|---|---|
| Principal Product | Rubber Products |
| NAICS |
n/a
|
| SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 175 |
| Plant Area |
137,500
ft2
|
| Annual Production | 2,250,000
lb
|
| Production Hrs. Annual | 5,000
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $594,446 | 9,129,250 |
kWh
|
$0.065 |
| Natural Gas | $68,995 | 15,796 |
MMBtu
|
$4.37 |
| Other Energy | $152,675 | 136,317 |
MMBtu
|
$1.12 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $56,483 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $28,468 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Other Energy Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $21,000 | $45,000 |
$21,000
419,988
kWh
|
- | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $388 | $300 |
$388
6,741
kWh
|
- | - | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $580 | $588 |
$580
9,965
kWh
|
- | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $192 | $168 |
$192
3,224
kWh
|
- | - | |
| 05 | 2.7314: Reduce ventilation air | $782 | $1,250 | - | - |
$782
-
MMBtu
|
|
| 06 | 2.2511: Insulate bare equipment | $538 | $864 | - | - |
$538
-
MMBtu
|
|
| 07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $20,681 | $40,000 |
$42,241
746,190
kWh
|
- |
$(-21,560.0)
-
MMBtu
|
|
| 08 | 2.4131: Size electric motors for peak operating efficiency | $6,888 | $7,500 |
$6,888
137,749
kWh
|
- | - | |
| 09 | 2.1335: Replace gasoline with diesel, lpg, or natural gas | $5,434 | $7,200 | - |
$6,865
-
MMBtu
|
$(-1,431.0)
-
MMBtu
|
|
| TOTAL RECOMMENDED | $56,483 | $102,870 |
$71,289
1,323,857
kWh
|
$6,865
-
MMBtu
|
$(-21,671.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $28,468 | $52,968 |
$28,468
567,702
kWh
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Other Energy Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs