Assessment Year | 1983 |
---|---|
Principal Product | AUTOMOTIVE BATTERIES |
NAICS |
n/a
|
SIC | 3691: Storage Batteries |
Sales Range | $10 M to 50M |
# of Employees | 185 |
Plant Area |
n/a
|
Annual Production | 700,000
pieces
|
Production Hrs. Annual | 5,440
hrs
|
Location (State) | Kansas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $257,296 | 6,591,442 |
kWh
|
$0.039 |
Natural Gas | $53,088 | 22,617 |
MMBtu
|
$2.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,791 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,791 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,345 | $2,826 |
$2,345
60,082
kWh
|
- | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $961 | $1,200 | - |
$961
-
MMBtu
|
|
03 | 2.4239: Eliminate or reduce compressed air usage | $3,626 | $100 |
$3,626
92,907
kWh
|
- | |
04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $354 | $74 | - |
$354
-
MMBtu
|
|
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $284 | $300 | - |
$284
-
MMBtu
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $221 | $60 |
$221
5,569
kWh
|
- | |
TOTAL RECOMMENDED | $7,791 | $4,560 |
$6,192
158,558
kWh
|
$1,599
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,791 | $4,560 |
$6,192
158,558
kWh
|
$1,599
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs