Assessment Year | 2025 |
---|---|
Principal Product | Fabricated Pipe Fittings |
NAICS | 332996: Fabricated Pipe and Pipe Fitting Manufacturing |
SIC | 3498: Fabricated Pipe and Pipe Fittings |
Sales Range | $10 M to 50M |
# of Employees | 81 |
Plant Area |
35,000
ft2
|
Annual Production | 250,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $47,180 | 686,280 |
kWh
|
$0.069 |
Electricity Demand | $59,366 | 2,301 |
kW-mo/yr
|
$25.80 |
TOTAL YEARLY COSTS | $106,546 | |||
RECOMMENDED SAVINGS* | $31,279 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,169 | $4,040 |
$550
8,000
kWh
|
$619
-
kW-mo/yr
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $834 | $90 |
$290
4,216
kWh
|
$544
-
kW-mo/yr
|
|
03 | 2.7442: Keep doors and windows shut when not on use | $597 | - |
$334
4,864
kWh
|
$263
-
kW-mo/yr
|
|
04 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $1,393 | $3,705 |
$578
8,420
kWh
|
$815
-
kW-mo/yr
|
|
05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,807 | - | - |
$2,807
-
kW-mo/yr
|
|
06 | 2.9114: Use solar heat to make electricty | $24,479 | $193,329 |
$15,129
220,223
kWh
|
$9,350
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $31,279 | $201,164 |
$16,881
245,723
kWh
|
$14,398
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs