| Assessment Year | 1997 |
|---|---|
| Principal Product | Soft Drinks |
| NAICS |
n/a
|
| SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
| Sales Range | $10 M to 50M |
| # of Employees | 250 |
| Plant Area |
175,000
ft2
|
| Annual Production | 10,000,000
pieces
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $127,247 | 4,108,441 |
kWh
|
$0.031 |
| Electricity Demand | $77,984 | 11,701 |
kW-mo/yr
|
$6.66 |
| Electricity Fees | $6,717 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $111,731 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $63,829 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $14,215 | $3,800 |
$10,454
338,218
kWh
|
$3,761
-
kW-mo/yr
|
- | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,994 | $20,000 |
$8,950
179,074
kWh
|
$2,044
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,097 | $23,240 |
$7,064
228,605
kWh
|
$2,033
-
kW-mo/yr
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,404 | $922 |
$1,676
54,220
kWh
|
$728
-
kW-mo/yr
|
- | - | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,439 | $2,190 |
$1,439
46,600
kWh
|
- | - | - | |
| 06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,258 | $1,150 |
$1,258
40,739
kWh
|
- | - | - | |
| 07 | 2.7261: Install timers and/or thermostats | $1,209 | $750 |
$1,209
41,618
kWh
|
- | - | - | |
| 08 | 2.2414: Use waste heat from hot flue gases to preheat | $1,072 | $4,550 |
$1,072
97,304
kWh
|
- | - | - | |
| 09 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $409 | $315 |
$409
13,189
kWh
|
- | - | - | |
| 10 | 3.4151: Minimize water usage | $33,988 | $2,930 | - | - |
$33,988
-
Tgal
|
- | |
| 11 | 3.5313: Increase amount of waste recovered for resale | $34,825 | $500 | - | - | - |
$34,825
-
lb
|
|
| 12 | 3.4154: Eliminate leaks in water lines and valves | $821 | - | - | - |
$821
-
Tgal
|
- | |
| TOTAL RECOMMENDED | $111,731 | $60,347 |
$33,531
1,039,567
kWh
|
$8,566
-
kW-mo/yr
|
$34,809
-
Tgal
|
$34,825
-
lb
|
||
| TOTAL IMPLEMENTED | $63,829 | $30,362 |
$21,661
703,400
kWh
|
$6,522
-
kW-mo/yr
|
$821
-
Tgal
|
$34,825
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs