Assessment Year | 1995 |
---|---|
Principal Product | Pigments |
NAICS |
n/a
|
SIC | 2816: Inorganic Pigments |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
125,937
ft2
|
Annual Production | 40,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $246,262 | 2,659,437 |
kWh
|
$0.093 |
Natural Gas | $676,056 | 274,370 |
MMBtu
|
$2.46 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,019 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,215 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $13,216 | $4,500 | - |
$13,216
-
MMBtu
|
|
02 | 2.4133: Use most efficient type of electric motors | $9,454 | $24,440 |
$9,454
157,386
kWh
|
- | |
03 | 2.2515: Use optimum thickness insulation | $2,733 | $2,269 | - |
$2,733
-
MMBtu
|
|
04 | 2.7261: Install timers and/or thermostats | $1,327 | $600 |
$1,327
40,152
kWh
|
- | |
05 | 2.7134: Use photocell controls | $1,206 | $945 |
$1,206
10,551
kWh
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,071 | $260 |
$1,071
17,878
kWh
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,012 | $467 |
$1,012
9,672
kWh
|
- | |
TOTAL RECOMMENDED | $30,019 | $33,481 |
$14,070
235,639
kWh
|
$15,949
-
MMBtu
|
||
TOTAL IMPLEMENTED | $26,215 | $30,952 |
$12,999
217,761
kWh
|
$13,216
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs