| Assessment Year | 2017 |
|---|---|
| Principal Product | Metal Formed Components |
| NAICS | 332111: Iron and Steel Forging |
| SIC | 3542: Machine Tools, Metal Forming Types |
| Sales Range | $10 M to 50M |
| # of Employees | 129 |
| Plant Area |
81,500
ft2
|
| Annual Production | 69,615,000
lb
|
| Production Hrs. Annual | 4,992
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,015,585 | 13,838,400 |
kWh
|
$0.073 |
| Electricity Demand | $649,062 | 54,662 |
kW-mo/yr
|
$11.87 |
| Electricity Fees | $4,308 | - |
|
- |
| Natural Gas | $32,254 | 5,728 |
MMBtu
|
$5.63 |
| TOTAL YEARLY COSTS | $1,701,209 | |||
| RECOMMENDED SAVINGS* | $113,923 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $107,216 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 4.821: Pay bills on time to avoid late fees | $4,308 | - | - | - | - | $4,308 | |
| 02 | 2.4323: Use optimum size and capacity equipment | $2,245 | - |
$1,837
25,029
kWh
|
$408
-
kW-mo/yr
|
- | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,092 | - |
$1,092
14,877
kWh
|
- | - | - | |
| 04 | 2.7221: Lower temperature during the winter season and vice-versa | $15,443 | $240 |
$8,208
111,840
kWh
|
- |
$7,235
-
MMBtu
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $19,611 | $410 |
$18,996
258,835
kWh
|
$615
-
kW-mo/yr
|
- | - | |
| 06 | 2.7135: Install occupancy sensors | $5,853 | $469 |
$5,853
77,756
kWh
|
- | - | - | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $26,601 | $3,039 |
$22,480
306,309
kWh
|
$4,121
-
kW-mo/yr
|
- | - | |
| 08 | 2.4322: Use or replace with energy efficient substitutes | $10,674 | $2,715 |
$10,674
145,439
kWh
|
- | - | - | |
| 09 | 2.4322: Use or replace with energy efficient substitutes | $9,248 | $5,271 |
$9,647
131,461
kWh
|
$(-399.0)
-
kW-mo/yr
|
- | - | |
| 10 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $12,141 | $13,384 |
$5,961
81,226
kWh
|
$6,180
-
kW-mo/yr
|
- | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,813 | $11,115 |
$3,486
47,500
kWh
|
$2,327
-
kW-mo/yr
|
- | - | |
| 12 | 2.7241: Install outside air damper / economizer on hvac unit | $894 | $2,116 |
$894
12,177
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $113,923 | $38,759 |
$89,128
1,212,449
kWh
|
$13,252
-
kW-mo/yr
|
$7,235
-
MMBtu
|
$4,308 | ||
| TOTAL IMPLEMENTED | $107,216 | $25,528 |
$84,748
1,152,772
kWh
|
$10,925
-
kW-mo/yr
|
$7,235
-
MMBtu
|
$4,308 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs