Assessment Year | 2015 |
---|---|
Principal Product | Sheet Metal Fabricated Enclosures |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 193 |
Plant Area |
107,300
ft2
|
Annual Production | 200
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $92,266 | 1,708,200 |
kWh
|
$0.054 |
Electricity Demand | $103,772 | 6,787 |
kW-mo/yr
|
$15.29 |
Electricity Fees | $23,519 | - |
|
- |
Natural Gas | $52,407 | 7,283 |
MMBtu
|
$7.20 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $51,386 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $41,478 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $3,077 | $47 | - | - |
$3,077
-
MMBtu
|
- | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $437 | $9 |
$437
8,096
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,655 | $61 |
$1,655
30,633
kWh
|
- | - | - | - | |
04 | 2.3192: Use fossil fuel powered generator during peak demand periods | $12,878 | $902 |
$12,878
238,450
kWh
|
- | - | - | - | |
05 | 2.2511: Insulate bare equipment | $6,052 | $2,650 | - | - |
$6,052
-
MMBtu
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $1,932 | $953 |
$1,251
23,166
kWh
|
$681
-
kW-mo/yr
|
- | - | - | |
07 | 2.3192: Use fossil fuel powered generator during peak demand periods | $10,505 | $7,153 |
$1,321
24,464
kWh
|
$26,834
-
kW-mo/yr
|
- | - | $(-17,650.0) | |
08 | 4.812: Apply for investment incentives | $12,926 | $10,000 | - | - | - | $12,926 | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,874 | $4,725 |
$(-63.0)
(-1,164)
kWh
|
- |
$1,937
-
MMBtu
|
- | - | |
10 | 2.7135: Install occupancy sensors | $50 | $179 |
$50
914
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $51,386 | $26,679 |
$17,529
324,559
kWh
|
$27,515
-
kW-mo/yr
|
$11,066
-
MMBtu
|
$12,926 | $(-17,650.0) | ||
TOTAL IMPLEMENTED | $41,478 | $18,172 |
$16,291
301,643
kWh
|
$26,834
-
kW-mo/yr
|
$3,077
-
MMBtu
|
$12,926 | $(-17,650.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs