Assessment Year | 2025 |
---|---|
Principal Product | Printed/Etched Retail Products |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $100 M to 500M |
# of Employees | 326 |
Plant Area |
361,000
ft2
|
Annual Production | 12,000,000
units
|
Production Hrs. Annual | 4,833
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $188,461 | 5,494,129 |
kWh
|
$0.034 | |
Electricity Demand | $195,473 | 14,819 |
kW-mo/yr
|
$13.19 | |
Electricity Fees | $142,097 | - |
|
- | |
Natural Gas | $54,942 | 9,772 |
MMBtu
|
$5.62 | |
Waste Disposal Costs | |||||
Water Usage | $39,258 | 2,108 |
Tgal
|
$18.63 | |
TOTAL YEARLY COSTS | $620,231 | ||||
RECOMMENDED SAVINGS* | $81,371 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.3191: Use demand controller or load shedder | $5,393 | $16,567 |
$2,246
66,068
kWh
|
- |
$3,147
-
MMBtu
|
|
02 | 2.6231: Utilize controls to operate equipment only when needed | $9,099 | $14,469 |
$5,510
162,048
kWh
|
$3,590
-
kW-mo/yr
|
- | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $8,428 | - | - |
$8,428
-
kW-mo/yr
|
- | |
04 | 2.4239: Eliminate or reduce compressed air usage | $2,018 | $5,197 |
$1,054
30,992
kWh
|
$964
-
kW-mo/yr
|
- | |
05 | 2.4239: Eliminate or reduce compressed air usage | $275 | - |
$275
8,008
kWh
|
- | - | |
06 | 2.7135: Install occupancy sensors | $2,117 | $2,486 |
$681
20,043
kWh
|
$1,436
-
kW-mo/yr
|
- | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $295 | $481 |
$18
528
kWh
|
$277
-
kW-mo/yr
|
- | |
08 | 2.4322: Use or replace with energy efficient substitutes | $10,088 | $20,716 |
$3,077
90,511
kWh
|
$7,011
-
kW-mo/yr
|
- | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,027 | - |
$1,542
45,341
kWh
|
$1,485
-
kW-mo/yr
|
- | |
10 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $4,445 | $3,414 | - | - |
$4,445
-
MMBtu
|
|
11 | 2.4239: Eliminate or reduce compressed air usage | $33,790 | $16,614 |
$2,457
72,255
kWh
|
$31,333
-
kW-mo/yr
|
- | |
12 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $1,597 | $5,347 | - | - |
$1,597
-
MMBtu
|
|
13 | 2.4221: Install compressor air intakes in coolest locations | $799 | $519 |
$407
11,968
kWh
|
$393
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $81,371 | $85,809 |
$17,267
507,763
kWh
|
$54,915
-
kW-mo/yr
|
$9,189
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs