Assessment Year | 2024 |
---|---|
Principal Product | Container Lids |
NAICS | 332431: Metal Can Manufacturing |
SIC | 3411: Metal Cans |
Sales Range | $50 M to 100M |
# of Employees | 120 |
Plant Area |
200,000
ft2
|
Annual Production | 1,235,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $251,836 | 2,759,244 |
kWh
|
$0.091 |
Electricity Demand | $90,627 | 7,796 |
kW-mo/yr
|
$11.62 |
Electricity Fees | $21,478 | - |
|
- |
Natural Gas | $50,117 | 7,389 |
MMBtu
|
$6.78 |
TOTAL YEARLY COSTS | $414,058 | |||
RECOMMENDED SAVINGS* | $382,333 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $26,380 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $341,931 | $2,037,172 |
$197,262
2,167,719
kWh
|
$144,669
-
kW-mo/yr
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $3,300 | $1,110 |
$2,649
29,112
kWh
|
$651
-
kW-mo/yr
|
- | |
03 | 2.4226: Use / purchase optimum sized compressor | $13,885 | $54,145 |
$11,148
122,501
kWh
|
$2,737
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $384 | $338 |
$384
4,219
kWh
|
- | - | |
05 | 2.2515: Use optimum thickness insulation | $17,140 | $38,685 |
$1,308
14,378
kWh
|
$11,676
-
kW-mo/yr
|
$4,156
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,336 | $6,391 |
$3,253
35,747
kWh
|
$1,084
-
kW-mo/yr
|
- | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $137 | $495 |
$114
1,250
kWh
|
$24
-
kW-mo/yr
|
- | |
08 | 2.7441: Replace broken windows and/or window sash | $1,219 | $3,519 |
$55
609
kWh
|
$494
-
kW-mo/yr
|
$669
-
MMBtu
|
|
TOTAL RECOMMENDED | $382,333 | $2,141,854 |
$216,174
2,375,535
kWh
|
$161,334
-
kW-mo/yr
|
$4,826
-
MMBtu
|
||
TOTAL IMPLEMENTED | $26,380 | $50,043 |
$7,650
84,065
kWh
|
$13,904
-
kW-mo/yr
|
$4,826
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs