| Assessment Year | 2011 |
|---|---|
| Principal Product | Gears |
| NAICS | 332111: Iron and Steel Forging |
| SIC | 3462: Iron and Steel Forgings |
| Sales Range | $1 M to 5M |
| # of Employees | 120 |
| Plant Area |
157,950
ft2
|
| Annual Production | 4,000,000
pieces
|
| Production Hrs. Annual | 7,224
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $824,370 | 17,687,015 |
kWh
|
$0.047 |
| Electricity Demand | $391,268 | 56,148 |
kW-mo/yr
|
$6.97 |
| Electricity Fees | $4,228 | - |
|
- |
| Natural Gas | $120,156 | 17,272 |
MMBtu
|
$6.96 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $56,571 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $537 | $695 |
$198
3,986
kWh
|
$40
-
kW-mo/yr
|
- | $299 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,115 | $3,977 |
$654
13,938
kWh
|
$190
-
kW-mo/yr
|
- | $271 | |
| 03 | 2.7135: Install occupancy sensors | $963 | $1,463 |
$773
16,462
kWh
|
$190
-
kW-mo/yr
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,842 | $32,631 |
$11,738
249,710
kWh
|
$2,890
-
kW-mo/yr
|
- | $(-1,786.0) | |
| 05 | 2.2511: Insulate bare equipment | $766 | $350 | - | - |
$766
-
MMBtu
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $5,423 | $2,049 |
$4,350
92,557
kWh
|
$1,073
-
kW-mo/yr
|
- | - | |
| 07 | 2.4323: Use optimum size and capacity equipment | $6,206 | $11,658 |
$4,979
105,952
kWh
|
$1,227
-
kW-mo/yr
|
- | - | |
| 08 | 2.4226: Use / purchase optimum sized compressor | $26,660 | $128,000 |
$21,390
455,112
kWh
|
$5,270
-
kW-mo/yr
|
- | - | |
| 09 | 2.3132: Recharge batteries on during off-peak demand periods | $1,770 | $140 | - |
$1,770
-
kW-mo/yr
|
- | - | |
| 10 | 2.6211: Conserve energy by efficient use of vending machines | $289 | - |
$240
5,100
kWh
|
$49
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $56,571 | $180,963 |
$44,322
942,817
kWh
|
$12,699
-
kW-mo/yr
|
$766
-
MMBtu
|
$(-1,216.0) | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs