Assessment Year | 2016 |
---|---|
Principal Product | Plastic Bags |
NAICS | 326111: Plastics Bag and Pouch Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $5 M to 10M |
# of Employees | 29 |
Plant Area |
60,000
ft2
|
Annual Production | 4,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Iowa |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $108,546 | 1,982,567 |
kWh
|
$0.055 |
Electricity Demand | $49,229 | 4,860 |
kW-mo/yr
|
$10.13 |
Natural Gas | $6,715 | 1,183 |
MMBtu
|
$5.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,732 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,230 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,261 | $40,935 |
$8,823
160,659
kWh
|
$4,438
-
kW-mo/yr
|
- | - | |
02 | 2.4133: Use most efficient type of electric motors | $7,170 | $20,053 |
$5,290
96,346
kWh
|
$1,880
-
kW-mo/yr
|
- | - | |
03 | 2.8121: Apply for tax-free status for energy purchases | $7,003 | $600 | - | - | - | $7,003 | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,334 | $527 |
$1,721
31,322
kWh
|
$613
-
kW-mo/yr
|
- | - | |
05 | 2.7135: Install occupancy sensors | $1,596 | $3,880 |
$1,596
29,053
kWh
|
- | - | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $745 | $650 |
$550
9,985
kWh
|
$195
-
kW-mo/yr
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $730 | $450 |
$535
9,755
kWh
|
$195
-
kW-mo/yr
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $564 | $24 |
$444
8,100
kWh
|
$120
-
kW-mo/yr
|
- | - | |
09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $490 | $500 | - | - |
$490
-
MMBtu
|
- | |
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $465 | $30 |
$343
6,240
kWh
|
$122
-
kW-mo/yr
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $374 | $663 |
$374
6,797
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $34,732 | $68,312 |
$19,676
358,257
kWh
|
$7,563
-
kW-mo/yr
|
$490
-
MMBtu
|
$7,003 | ||
TOTAL IMPLEMENTED | $11,230 | $2,344 |
$2,882
52,459
kWh
|
$855
-
kW-mo/yr
|
$490
-
MMBtu
|
$7,003 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs