Assessment Year | 2011 |
---|---|
Principal Product | Automotive Locking Mechanism |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3429: Hardware, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 440 |
Plant Area |
325,000
ft2
|
Annual Production | 11,900,000
pieces
|
Production Hrs. Annual | 5,880
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $447,590 | 13,514,048 |
kWh
|
$0.033 |
Electricity Demand | $627,820 | 46,402 |
kW-mo/yr
|
$13.53 |
Electricity Fees | $36,140 | - |
|
- |
Natural Gas | $323,987 | 40,816 |
MMBtu
|
$7.94 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $250,735 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $126,419 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,634 | - |
$18,634
562,970
kWh
|
- | - | - | $(-5,000.0) | |
02 | 2.6231: Utilize controls to operate equipment only when needed | $7,201 | - |
$7,201
217,560
kWh
|
- | - | - | - | |
03 | 2.2628: Utilize a less expensive cooling method | $28,143 | $70,000 |
$4,601
139,010
kWh
|
$23,542
-
kW-mo/yr
|
- | - | - | |
04 | 3.4155: Meter waste water | $3,614 | $6,000 | - | - | - |
$3,614
-
Tgal
|
- | |
05 | 2.4224: Upgrade controls on compressors | $16,076 | $55,000 |
$16,076
485,673
kWh
|
- | - | - | - | |
06 | 2.7224: Reduce space conditioning during non-working hours | $31,792 | $136,000 |
$31,792
960,476
kWh
|
- | - | - | - | |
07 | 2.4322: Use or replace with energy efficient substitutes | $17,800 | $38,640 |
$17,800
537,772
kWh
|
- | - | - | - | |
08 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $85,358 | $222,000 |
$2,671
80,706
kWh
|
- |
$82,687
-
MMBtu
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $47,117 | $155,150 |
$28,283
854,462
kWh
|
$18,834
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $250,735 | $682,790 |
$127,058
3,838,629
kWh
|
$42,376
-
kW-mo/yr
|
$82,687
-
MMBtu
|
$3,614
-
Tgal
|
$(-5,000.0) | ||
TOTAL IMPLEMENTED | $126,419 | $384,790 |
$112,585
3,401,353
kWh
|
$18,834
-
kW-mo/yr
|
- | - | $(-5,000.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs