| Assessment Year | 1995 |
|---|---|
| Principal Product | Mowers, Ditchers |
| NAICS |
n/a
|
| SIC | 3524: Lawn and Garden Tractors and Home Lawn and Garden Equipment |
| Sales Range | $1 M to 5M |
| # of Employees | 150 |
| Plant Area |
62,906
ft2
|
| Annual Production | 1,000
pieces
|
| Production Hrs. Annual | 3,120
hrs
|
| Location (State) | South Dakota |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $23,899 | 331,770 |
kWh
|
$0.072 |
| Natural Gas | $9,920 | 2,134 |
MMBtu
|
$4.65 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $7,467 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $367 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,787 | $8,639 |
$2,787
38,394
kWh
|
- | |
| 02 | 2.7135: Install occupancy sensors | $305 | $900 |
$305
9,086
kWh
|
- | |
| 03 | 2.7261: Install timers and/or thermostats | $1,567 | $1,050 | - |
$1,567
-
MMBtu
|
|
| 04 | 2.7231: Use radiant heater for spot heating | $2,387 | $6,000 | - |
$2,387
-
MMBtu
|
|
| 05 | 2.4133: Use most efficient type of electric motors | $367 | $970 |
$367
3,517
kWh
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $54 | $168 |
$54
1,465
kWh
|
- | |
| TOTAL RECOMMENDED | $7,467 | $17,727 |
$3,513
52,462
kWh
|
$3,954
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $367 | $970 |
$367
3,517
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs