Assessment Year | 2012 |
---|---|
Principal Product | Cigarettes |
NAICS | 312230: Tobacco Manufacturing |
SIC | 2111: Cigarettes |
Sales Range | greater than $500 M |
# of Employees | 1,200 |
Plant Area |
1,180,613
ft2
|
Annual Production | 38,000,000,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,495,028 | 62,836,400 |
kWh
|
$0.040 |
Electricity Demand | $1,054,554 | 123,168 |
kW-mo/yr
|
$8.56 |
Electricity Fees | $6,619 | - |
|
- |
Natural Gas | $1,648,438 | 272,920 |
MMBtu
|
$6.04 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $398,193 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $212,900 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $50,793 | $243,606 |
$40,042
1,001,040
kWh
|
$10,751
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $90,894 | $148,184 |
$73,388
1,834,694
kWh
|
$19,701
-
kW-mo/yr
|
- | - | - | $(-2,195.0) | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,310 | $2,810 |
$676
16,900
kWh
|
$182
-
kW-mo/yr
|
- | - | - | $1,452 | |
04 | 2.7135: Install occupancy sensors | $17,141 | $6,600 |
$17,141
428,523
kWh
|
- | - | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,566 | $100 |
$5,489
137,234
kWh
|
$1,477
-
kW-mo/yr
|
- | - | $(-1,200.0) | $(-1,200.0) | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $121,439 | $199,600 | - | - |
$121,439
-
MMBtu
|
- | - | - | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,568 | $2,700 | - | - |
$5,568
-
MMBtu
|
- | - | - | |
08 | 2.2121: Increase amount of condensate returned | $22,095 | $21,000 | - | - |
$11,231
-
MMBtu
|
$10,364
-
Tgal
|
- | $500 | |
09 | 2.2113: Repair or replace steam traps | $19,533 | $16,000 | - | - |
$19,533
-
MMBtu
|
- | - | - | |
10 | 2.7242: Change zone reheat coils to variable air volume boxes | $63,854 | $140,000 |
$12,836
369,542
kWh
|
- |
$51,018
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $398,193 | $780,600 |
$149,572
3,787,933
kWh
|
$32,111
-
kW-mo/yr
|
$208,789
-
MMBtu
|
$10,364
-
Tgal
|
$(-1,200.0) | $(-1,443.0) | ||
TOTAL IMPLEMENTED | $212,900 | $441,000 |
$136,736
3,418,391
kWh
|
$32,111
-
kW-mo/yr
|
$36,332
-
MMBtu
|
$10,364
-
Tgal
|
$(-1,200.0) | $(-1,443.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs