| Assessment Year | 2026 |
|---|---|
| Principal Product | sanitary personal care products |
| NAICS | 322291: Sanitary Paper Product Manufacturing |
| SIC | 2676: Sanitary Paper Products |
| Sales Range | $100 M to 500M |
| # of Employees | 400 |
| Plant Area |
500,000
ft2
|
| Annual Production | 3,160,000,000
units
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Delaware |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,825,963 | 37,814,451 |
kWh
|
$0.075 |
| Electricity Demand | $720,008 | 66,565 |
kW-mo/yr
|
$10.82 |
| Electricity Fees | $6,424 | - |
|
- |
| Natural Gas | $82,745 | 7,300 |
MMBtu
|
$11.33 |
| TOTAL YEARLY COSTS | $3,635,140 | |||
| RECOMMENDED SAVINGS* | $184,569 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $78,750 | $30,000 |
$78,750
1,050,000
kWh
|
|
| 02 | 2.4226: Use / purchase optimum sized compressor | $60,870 | - |
$60,870
811,600
kWh
|
|
| 03 | 2.4235: Remove or close off unneeded compressed air lines | $40,280 | - |
$40,280
537,100
kWh
|
|
| 04 | 2.7261: Install timers and/or thermostats | $4,669 | - |
$4,669
62,250
kWh
|
|
| TOTAL RECOMMENDED | $184,569 | $30,000 |
$184,569
2,460,950
kWh
|
||
| TOTAL IMPLEMENTED | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs