| Assessment Year | 2026 |
|---|---|
| Principal Product | plastic bottles |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 100 |
| Plant Area |
185,000
ft2
|
| Annual Production | 26,000,000
units
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Maryland |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,028,416 | 7,769,279 |
kWh
|
$0.13 |
| Electricity Demand | $80,171 | 18,218 |
kW-mo/yr
|
$4.40 |
| Electricity Fees | $466 | - |
|
- |
| Natural Gas | $21,178 | 1,534 |
MMBtu
|
$13.81 |
| Other Gas | $811 | 1 |
MMBtu
|
$811.00 |
| TOTAL YEARLY COSTS | $1,131,042 | |||
| RECOMMENDED SAVINGS* | $192,376 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $15,901 | - |
$15,901
111,198
kWh
|
- | |
| 02 | 2.7261: Install timers and/or thermostats | $6,701 | $30 |
$6,701
46,857
kWh
|
- | |
| 03 | 2.6231: Utilize controls to operate equipment only when needed | $20,035 | - |
$20,035
140,105
kWh
|
- | |
| 04 | 2.6231: Utilize controls to operate equipment only when needed | $2,314 | - |
$1,071
7,493
kWh
|
$1,243
-
MMBtu
|
|
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,597 | $32,200 |
$13,597
95,083
kWh
|
- | |
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,544 | $32,500 |
$15,544
108,701
kWh
|
- | |
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $113,285 | $546,000 |
$113,285
792,201
kWh
|
- | |
| 08 | 2.7261: Install timers and/or thermostats | $4,999 | $220 | - |
$4,999
-
MMBtu
|
|
| TOTAL RECOMMENDED | $192,376 | $610,950 |
$186,134
1,301,638
kWh
|
$6,242
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs