Assessment Year | 2025 |
---|---|
Principal Product | Polymer Rods |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $5 M to 10M |
# of Employees | 25 |
Plant Area |
23,000
ft2
|
Annual Production | 200,000
lb
|
Production Hrs. Annual | 5,953
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $89,068 | 909,477 |
kWh
|
$0.098 |
Electricity Demand | $59,711 | 3,085 |
kW-mo/yr
|
$19.36 |
Electricity Fees | $2,934 | - |
|
- |
Natural Gas | $1,213 | 140 |
MMBtu
|
$8.66 |
TOTAL YEARLY COSTS | $152,926 | |||
RECOMMENDED SAVINGS* | $28,192 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6231: Utilize controls to operate equipment only when needed | $2,580 | - |
$1,957
19,969
kWh
|
$623
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,209 | $291 |
$3,113
31,763
kWh
|
$2,096
-
kW-mo/yr
|
- | |
03 | 2.2511: Insulate bare equipment | $5,964 | $373 |
$3,571
36,435
kWh
|
$2,393
-
kW-mo/yr
|
- | |
04 | 2.4226: Use / purchase optimum sized compressor | $4,139 | $10,680 |
$2,474
25,243
kWh
|
$1,665
-
kW-mo/yr
|
- | |
05 | 2.2211: Use optimum temperature | $1,534 | $550 |
$797
8,130
kWh
|
$536
-
kW-mo/yr
|
$201
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,995 | $4,980 |
$5,718
58,344
kWh
|
$2,277
-
kW-mo/yr
|
- | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $771 | $736 |
$392
3,998
kWh
|
$379
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $28,192 | $17,610 |
$18,022
183,882
kWh
|
$9,969
-
kW-mo/yr
|
$201
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs