Assessment Year | 2022 |
---|---|
Principal Product | Food processing equipment |
NAICS | 333318: Other Commercial and Service Industry Machinery Manufacturing |
SIC | 3589: Service Industry Machinery, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 350 |
Plant Area |
375,000
ft2
|
Annual Production | 485,912
units
|
Production Hrs. Annual | 4,375
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $299,406 | 4,388,315 |
kWh
|
$0.068 | |
Electricity Demand | $66,045 | 12,650 |
kW-mo/yr
|
$5.22 | |
Electricity Fees | $7,898 | - |
|
- | |
Natural Gas | $75,372 | 7,459 |
MMBtu
|
$10.10 | |
Waste Disposal Costs | |||||
Water Usage | $18,812 | 1,612 |
Tgal
|
$11.67 | |
TOTAL YEARLY COSTS | $467,533 | ||||
RECOMMENDED SAVINGS* | $108,608 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $66,863 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2443: Re-use or recycle hot or cold process exhaust air | $25,361 | $3,000 | - | - |
$25,361
-
MMBtu
|
|
02 | 2.7311: Ventilation system to shut off when room is not in use | $8,504 | - | - | - |
$8,504
-
MMBtu
|
|
03 | 2.7314: Reduce ventilation air | $4,894 | - |
$4,010
58,963
kWh
|
$885
-
kW-mo/yr
|
- | |
04 | 2.6218: Turn off equipment when not in use | $583 | - |
$478
7,026
kWh
|
$105
-
kW-mo/yr
|
- | |
05 | 2.7261: Install timers and/or thermostats | $3,567 | $71 |
$705
10,363
kWh
|
$155
-
kW-mo/yr
|
$2,707
-
MMBtu
|
|
06 | 2.7261: Install timers and/or thermostats | $627 | $96 |
$514
7,552
kWh
|
$113
-
kW-mo/yr
|
- | |
07 | 2.4226: Use / purchase optimum sized compressor | $23,194 | $11,933 |
$19,003
279,450
kWh
|
$4,191
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,331 | $2,230 |
$1,910
28,086
kWh
|
$421
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $24,770 | $33,570 |
$20,294
298,432
kWh
|
$4,476
-
kW-mo/yr
|
- | |
10 | 2.4322: Use or replace with energy efficient substitutes | $11,982 | $55,000 |
$9,817
144,360
kWh
|
$2,166
-
kW-mo/yr
|
- | |
11 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,359 | $7,840 |
$4,018
59,087
kWh
|
$886
-
kW-mo/yr
|
$(-2,545.0)
-
MMBtu
|
|
12 | 2.4322: Use or replace with energy efficient substitutes | $436 | $2,500 |
$357
5,256
kWh
|
$79
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $108,608 | $116,240 |
$61,105
898,575
kWh
|
$13,476
-
kW-mo/yr
|
$34,027
-
MMBtu
|
||
TOTAL IMPLEMENTED | $66,863 | $105,304 |
$52,564
772,973
kWh
|
$11,592
-
kW-mo/yr
|
$2,707
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs