| Assessment Year | 2021 |
|---|---|
| Principal Product | Dairy Products |
| NAICS | 311511: Fluid Milk Manufacturing |
| SIC | 2026: Fluid Milk |
| Sales Range | $1 M to 5M |
| # of Employees | 30 |
| Plant Area |
20,000
ft2
|
| Annual Production | 180
Tgal
|
| Production Hrs. Annual | 6,550
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $85,965 | 817,196 |
kWh
|
$0.11 | |
| Electricity Demand | $15,083 | 2,465 |
kW-mo/yr
|
$6.12 | |
| Electricity Fees | $4,450 | - |
|
- | |
| Natural Gas | $38,638 | 6,959 |
MMBtu
|
$5.55 | |
| Waste Disposal Costs | |||||
| Water Usage | $30,903 | 5,045 |
Tgal
|
$6.13 | |
| TOTAL YEARLY COSTS | $175,039 | ||||
| RECOMMENDED SAVINGS* | $29,578 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Usage Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.6231: Utilize controls to operate equipment only when needed | $2,696 | - |
$2,696
21,740
kWh
|
- | - | |
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $3,827 | - |
$3,827
31,041
kWh
|
- | - | |
| 03 | 2.7211: Clean and maintain refrigerant condensers and towers | $3,622 | $600 |
$3,622
29,208
kWh
|
- | - | |
| 04 | 2.2136: Install / repair insulation on steam lines | $818 | $168 | - |
$818
-
MMBtu
|
- | |
| 05 | 3.3132: Use reverse osmosis to concentrate material | $5,413 | $1,000 | - |
$3,091
-
MMBtu
|
$2,322
-
Tgal
|
|
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,208 | $38 |
$834
6,724
kWh
|
$374
-
MMBtu
|
- | |
| 07 | 2.2437: Recover waste heat from equipment | $1,032 | $4,500 | - |
$1,032
-
MMBtu
|
- | |
| 08 | 2.7261: Install timers and/or thermostats | $687 | $333 |
$89
707
kWh
|
$598
-
MMBtu
|
- | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,391 | $1,527 |
$1,391
10,653
kWh
|
- | - | |
| 10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,846 | $1,500 |
$1,846
14,885
kWh
|
- | - | |
| 11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,536 | $925 |
$1,536
12,390
kWh
|
- | - | |
| 12 | 2.2621: Modify refrigeration system to operate at a lower pressure | $5,502 | $22,000 |
$5,502
44,370
kWh
|
- | - | |
| TOTAL RECOMMENDED | $29,578 | $32,591 |
$21,343
171,718
kWh
|
$5,913
-
MMBtu
|
$2,322
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs