Assessment Year | 2015 |
---|---|
Principal Product | Pickles/Peppers/Sauces |
NAICS | 311941: Mayonnaise, Dressing, and Other Prepared Sauce Manufacturing |
SIC | 2035: Pickled Fruits and Vegetables, Vegetable Sauces and Seasonings, and Salad Dressings |
Sales Range | $50 M to 100M |
# of Employees | 100 |
Plant Area |
200,000
ft2
|
Annual Production | 4,000,000
pieces
|
Production Hrs. Annual | 5,600
hrs
|
Location (State) | Maryland |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $380,327 | 4,756,144 |
kWh
|
$0.080 |
Electricity Demand | $90,237 | 11,297 |
kW-mo/yr
|
$7.99 |
Electricity Fees | $10,197 | - |
|
- |
Natural Gas | $305,447 | 39,504 |
MMBtu
|
$7.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $221,550 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2112: Use correct size steam traps | $12,870 | $2,380 | - | - |
$12,870
-
MMBtu
|
- | |
02 | 3.7222: Minimize overflows by installing level controls | $37,680 | $12,400 | - | - |
$24,970
-
MMBtu
|
$12,710
-
Tgal
|
|
03 | 2.6231: Utilize controls to operate equipment only when needed | $60,250 | $20,000 |
$52,980
662,210
kWh
|
$7,270
-
kW-mo/yr
|
- | - | |
04 | 2.1212: Operate boilers on high fire setting | $10,860 | $4,610 | - | - |
$10,860
-
MMBtu
|
- | |
05 | 2.4224: Upgrade controls on compressors | $7,730 | $11,520 |
$5,800
72,510
kWh
|
$1,930
-
kW-mo/yr
|
- | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $9,550 | $14,400 |
$9,100
113,710
kWh
|
$450
-
kW-mo/yr
|
- | - | |
07 | 2.2694: Use highest temperature for chilling or cold storage | $1,970 | $4,480 |
$1,720
21,560
kWh
|
$250
-
kW-mo/yr
|
- | - | |
08 | 3.4151: Minimize water usage | $80,640 | $200,250 |
$(-5,280.0)
(-66,000)
kWh
|
$(-1,150.0)
-
kW-mo/yr
|
- |
$87,070
-
Tgal
|
|
TOTAL RECOMMENDED | $221,550 | $270,040 |
$64,320
803,990
kWh
|
$8,750
-
kW-mo/yr
|
$48,700
-
MMBtu
|
$99,780
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs