Assessment Year | 2012 |
---|---|
Principal Product | Poultry Products |
NAICS | 311615: Poultry Processing |
SIC | 2015: Poultry Slaughtering and Processing |
Sales Range | $500 k to 1M |
# of Employees | 1,200 |
Plant Area |
162,962
ft2
|
Annual Production | 54,600,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,575,902 | 27,897,000 |
kWh
|
$0.092 |
Electricity Demand | $596,544 | 59,196 |
kW-mo/yr
|
$10.08 |
Natural Gas | $711,488 | 99,616 |
MMBtu
|
$7.14 |
LPG | $108,779 | 4,745 |
MMBtu
|
$22.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $584,732 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $152,843 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $323,076 | $500,000 |
$323,076
2,834,000
kWh
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $51,870 | $24,400 |
$51,870
455,000
kWh
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $33,801 | $36,000 |
$33,801
296,500
kWh
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $40,818 | $54,000 |
$40,818
358,059
kWh
|
- | |
05 | 2.4222: Install adequate dryers on air lines to eliminate blowdown | $18,222 | $42,000 |
$18,222
159,840
kWh
|
- | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $24,850 | $4,500 |
$24,850
217,981
kWh
|
- | |
07 | 2.6231: Utilize controls to operate equipment only when needed | $28,257 | $28,000 |
$28,257
247,869
kWh
|
- | |
08 | 2.1116: Improve combustion control capability | $16,536 | $8,900 | - |
$16,536
-
MMBtu
|
|
09 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $16,536 | $25,000 | - |
$16,536
-
MMBtu
|
|
10 | 2.7314: Reduce ventilation air | $26,354 | $4,500 |
$26,354
231,175
kWh
|
- | |
11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,412 | $720 |
$4,412
38,700
kWh
|
- | |
TOTAL RECOMMENDED | $584,732 | $728,020 |
$551,660
4,839,124
kWh
|
$33,072
-
MMBtu
|
||
TOTAL IMPLEMENTED | $152,843 | $118,900 |
$152,843
1,340,734
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs