| Assessment Year | 2011 |
|---|---|
| Principal Product | Newspapers |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | greater than $500 M |
| # of Employees | 483 |
| Plant Area |
246,460
ft2
|
| Annual Production | 800,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,366,850 | 15,532,400 |
kWh
|
$0.088 |
| Natural Gas | $392,407 | 40,483 |
MMBtu
|
$9.69 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $297,790 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $151,769 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $20,592 | $3,200 |
$20,592
234,000
kWh
|
- | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $119,680 | $350,000 |
$119,680
1,360,000
kWh
|
- | |
| 03 | 2.6213: Turn off steam / hot water lines leading to space heating units | $63,615 | $100,500 | - |
$63,615
-
MMBtu
|
|
| 04 | 2.2443: Re-use or recycle hot or cold process exhaust air | $31,497 | $800 |
$4,849
55,100
kWh
|
$26,648
-
MMBtu
|
|
| 05 | 2.6231: Utilize controls to operate equipment only when needed | $21,318 | $1,600 | - |
$21,318
-
MMBtu
|
|
| 06 | 2.7232: Replace existing hvac unit with high efficiency model | $24,600 | $18,000 |
$44,000
500,000
kWh
|
$(-19,400.0)
-
MMBtu
|
|
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,771 | $11,600 |
$10,771
122,400
kWh
|
- | |
| 08 | 2.7442: Keep doors and windows shut when not on use | $5,717 | $900 | - |
$5,717
-
MMBtu
|
|
| TOTAL RECOMMENDED | $297,790 | $486,600 |
$199,892
2,271,500
kWh
|
$97,898
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $151,769 | $363,200 |
$130,451
1,482,400
kWh
|
$21,318
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs