Assessment Year 2010
Principal Product Lubricating Oils
NAICS 324191: Petroleum Lubricating Oil and Grease Manufacturing
SIC 2992: Lubricating Oils and Greases
Sales Range $100
M
to 500
M
# of Employees 130
Plant Area 1,650,000
ft2
Annual Production 95,000
Tgal
Production Hrs. Annual 6,240
hrs
Location (State) New Jersey

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $743,199 9,075,138
kWh
Natural Gas $539,696 67,231
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $504,753 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $206,204

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.2135: Repair and eliminate steam leaks $184,560 $1,200,000 - $184,560
-
MMBtu
02 2.6125: Keep equipment clean $162,929 $102,000 - $162,929
-
MMBtu
03 2.4226: Use / purchase optimum sized compressor $42,720 $1,940 $42,720
479,940
kWh
-
04 2.2511: Insulate bare equipment $45,700 $7,900 - $45,700
-
MMBtu
05 2.4239: Eliminate or reduce compressed air usage $14,000 $300 $14,000
158,000
kWh
-
06 2.2211: Use optimum temperature $7,644 $100 - $7,644
-
MMBtu
07 2.6231: Utilize controls to operate equipment only when needed $5,100 $100 $5,100
56,000
kWh
-
08 2.7142: Utilize higher efficiency lamps and/or ballasts $35,000 $94,500 $35,000
385,000
kWh
-
09 2.7142: Utilize higher efficiency lamps and/or ballasts $7,100 $58,000 $7,100
78,000
kWh
-
TOTAL RECOMMENDED $504,753 $1,464,840 $103,920
1,156,940
kWh
$400,833
-
MMBtu
TOTAL IMPLEMENTED $206,204 $1,200,400 $14,000
158,000
kWh
$192,204
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs