Assessment Year | 1996 |
---|---|
Principal Product | beef patties |
NAICS |
n/a
|
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $50 M to 100M |
# of Employees | 187 |
Plant Area |
100,000
ft2
|
Annual Production | 260,000,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Nebraska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $305,578 | 11,783,412 |
kWh
|
$0.026 |
Electricity Demand | $232,125 | 35,928 |
kW-mo/yr
|
$6.46 |
Electricity Fees | $(-5.0) | - |
|
- |
Natural Gas | $107,699 | 20,994 |
MMBtu
|
$5.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,266 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $18,170 | $21,300 | - |
$18,170
-
kW-mo/yr
|
- | - | - | - | - | |
02 | 3.4115: Recover and reuse cooling water | $5,106 | $5,000 |
$(-200.0)
(-7,913)
kWh
|
$(-120.0)
-
kW-mo/yr
|
- |
$3,716
-
Tgal
|
- | - |
$1,710
-
Tgal
|
|
03 | 2.4133: Use most efficient type of electric motors | $862 | $4,652 |
$628
24,326
kWh
|
$234
-
kW-mo/yr
|
- | - | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,058 | $3,561 |
$657
25,498
kWh
|
$401
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.7442: Keep doors and windows shut when not on use | $1,750 | $250 |
$540
20,809
kWh
|
$320
-
kW-mo/yr
|
$890
-
MMBtu
|
- | - | - | - | |
06 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $660 | $780 |
$440
16,999
kWh
|
$220
-
kW-mo/yr
|
- | - | - | - | - | |
07 | 3.8132: Use less toxic and volatile solvent substitutes | $1,210 | $1,400 | - | - | - | - |
$900
-
gal
|
$310 | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $450 | $320 |
$320
12,603
kWh
|
$130
-
kW-mo/yr
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $29,266 | $37,263 |
$2,385
92,322
kWh
|
$19,355
-
kW-mo/yr
|
$890
-
MMBtu
|
$3,716
-
Tgal
|
$900
-
gal
|
$310 |
$1,710
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs