Assessment Year 1992
Principal Product Typewriter ribbon
NAICS
n/a
SIC 3955: Carbon Paper and Inked Ribbons
Sales Range $10
M
to 50
M
# of Employees 250
Plant Area 150,000
ft2
Annual Production 15,000,000
pieces
Production Hrs. Annual 4,680
hrs
Location (State) Colorado

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $190,512 3,490,914
kWh
Natural Gas $34,606 8,828
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $27,870 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $27,870

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,620 $100 $2,620
48,066
kWh
- -
02 2.4221: Install compressor air intakes in coolest locations $1,410 $520 $1,410
25,791
kWh
- -
03 2.6212: Turn off equipment during breaks, reduce operating time $3,140 $990 $3,140
49,531
kWh
- -
04 2.7314: Reduce ventilation air $2,860 $1,000 - $2,860
-
MMBtu
-
05 2.7442: Keep doors and windows shut when not on use $1,540 $1,010 - $1,540
-
MMBtu
-
06 2.7444: Close holes and openings in building such as broken windows $550 $1,360 - $550
-
MMBtu
-
07 2.4133: Use most efficient type of electric motors $12,280 $12,630 $12,280
225,088
kWh
- -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $2,540 $2,730 $2,540
46,600
kWh
- -
09 2.7224: Reduce space conditioning during non-working hours $690 $1,050 $170
6,448
kWh
$520
-
MMBtu
-
10 2.8121: Apply for tax-free status for energy purchases $240 $250 - - $240
TOTAL RECOMMENDED $27,870 $21,640 $22,160
401,524
kWh
$5,470
-
MMBtu
$240
TOTAL IMPLEMENTED $27,870 $21,640 $22,160
401,524
kWh
$5,470
-
MMBtu
$240
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs