Assessment Year | 1992 |
---|---|
Principal Product | Injection Molded Plastic Products |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 250 |
Plant Area |
134,000
ft2
|
Annual Production | 4,400,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $356,460 | 7,355,803 |
kWh
|
$0.048 |
Natural Gas | $46,034 | 12,823 |
MMBtu
|
$3.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $47,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,180 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $7,020 | $1,250 |
$7,020
136,577
kWh
|
- | - | - | |
02 | 2.2612: Use cooling tower water instead of refrigeration | $2,990 | $1,800 |
$2,990
89,097
kWh
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,480 | $2,560 |
$3,480
71,805
kWh
|
- | - | - | |
04 | 2.7111: Reduce illumination to minimum necessary levels | $1,610 | $40 |
$1,610
48,066
kWh
|
- | - | - | |
05 | 2.1123: Install automatic stack damper | $6,430 | $6,000 | - |
$6,430
-
MMBtu
|
- | - | |
06 | 2.7243: Improve air circulation with destratification fans / other methods | $5,850 | $7,600 |
$(-130.0)
(-2,638)
kWh
|
$5,980
-
MMBtu
|
- | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $490 | $780 |
$490
9,965
kWh
|
- | - | - | |
08 | 2.7224: Reduce space conditioning during non-working hours | $590 | $1,350 |
$400
12,016
kWh
|
$190
-
MMBtu
|
- | - | |
09 | 2.4224: Upgrade controls on compressors | $5,970 | $12,000 |
$350
7,034
kWh
|
- | - | $5,620 | |
10 | 2.7442: Keep doors and windows shut when not on use | $230 | $530 | - |
$230
-
MMBtu
|
- | - | |
11 | 2.4133: Use most efficient type of electric motors | $3,470 | $6,280 |
$3,470
71,512
kWh
|
- | - | - | |
12 | 2.8114: Change rate schedules or other changes in utility service | $9,050 | $30,250 | - | - | $9,050 | - | |
TOTAL RECOMMENDED | $47,180 | $70,440 |
$19,680
443,434
kWh
|
$12,830
-
MMBtu
|
$9,050 | $5,620 | ||
TOTAL IMPLEMENTED | $47,180 | $70,440 |
$19,680
443,434
kWh
|
$12,830
-
MMBtu
|
$9,050 | $5,620 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs