Assessment Year | 1987 |
---|---|
Principal Product | FIBERGLASS ROOFING MATERIAL |
NAICS |
n/a
|
SIC | 2952: Asphalt Felts and Coatings |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
n/a
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $82,924 | 1,608,148 |
kWh
|
$0.052 |
Natural Gas | $119,687 | 30,535 |
MMBtu
|
$3.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,278 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,805 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,881 | $300 | - |
$6,881
-
MMBtu
|
|
02 | 2.1222: Install turbulators | $4,207 | $1,200 | - |
$4,207
-
MMBtu
|
|
03 | 2.2444: Use hot process fluids to preheat incoming process fluids | $2,330 | $5,000 | - |
$2,330
-
MMBtu
|
|
04 | 2.2511: Insulate bare equipment | $1,718 | $1,000 | - |
$1,718
-
MMBtu
|
|
05 | 2.2135: Repair and eliminate steam leaks | $2,812 | $500 | - |
$2,812
-
MMBtu
|
|
06 | 2.4221: Install compressor air intakes in coolest locations | $302 | $500 |
$302
6,448
kWh
|
- | |
07 | 2.4312: Improve lubrication practices | $150 | - |
$150
3,224
kWh
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $333 | $900 |
$333
7,034
kWh
|
- | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $397 | $20 |
$397
8,499
kWh
|
- | |
10 | 2.4322: Use or replace with energy efficient substitutes | $9,596 | $20,000 |
$9,596
186,108
kWh
|
- | |
11 | 2.6232: Install set-back timers | $552 | $395 |
$552
10,551
kWh
|
- | |
TOTAL RECOMMENDED | $29,278 | $29,815 |
$11,330
221,864
kWh
|
$17,948
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,805 | $4,795 |
$1,187
24,033
kWh
|
$15,618
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs