Assessment Year | 1986 |
---|---|
Principal Product | CORRUGATED BOXES |
NAICS |
n/a
|
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
n/a
|
Annual Production | 325,000
thousand feet
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $125,473 | 2,210,141 |
kWh
|
$0.057 |
Natural Gas | $141,078 | 35,446 |
MMBtu
|
$3.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $47,577 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $29,735 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,565 | $500 |
$11,565
203,693
kWh
|
- | |
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $10,145 | $300 | - |
$10,145
-
MMBtu
|
|
03 | 2.7243: Improve air circulation with destratification fans / other methods | $7,035 | $5,500 |
$(-483.0)
(-8,499)
kWh
|
$7,518
-
MMBtu
|
|
04 | 2.2414: Use waste heat from hot flue gases to preheat | $4,931 | $6,400 | - |
$4,931
-
MMBtu
|
|
05 | 2.2135: Repair and eliminate steam leaks | $2,145 | $1,000 | - |
$2,145
-
MMBtu
|
|
06 | 2.2121: Increase amount of condensate returned | $820 | $400 | - |
$820
-
MMBtu
|
|
07 | 2.4312: Improve lubrication practices | $3,461 | - |
$3,461
60,961
kWh
|
- | |
08 | 2.4221: Install compressor air intakes in coolest locations | $1,830 | $200 |
$1,830
32,239
kWh
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,464 | $1,800 |
$1,464
25,791
kWh
|
- | |
10 | 2.3132: Recharge batteries on during off-peak demand periods | $1,145 | $300 |
$1,145
-
kWh
|
- | |
11 | 2.7492: Use proper thickness of insulation on building envelope | $768 | $1,435 | - |
$768
-
MMBtu
|
|
12 | 2.2136: Install / repair insulation on steam lines | $454 | $630 | - |
$454
-
MMBtu
|
|
13 | 2.7444: Close holes and openings in building such as broken windows | $183 | $80 | - |
$183
-
MMBtu
|
|
14 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,631 | $2,970 |
$1,631
28,722
kWh
|
- | |
TOTAL RECOMMENDED | $47,577 | $21,515 |
$20,613
342,907
kWh
|
$26,964
-
MMBtu
|
||
TOTAL IMPLEMENTED | $29,735 | $6,300 |
$16,171
264,654
kWh
|
$13,564
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs