| Assessment Year | 1985 |
|---|---|
| Principal Product | AUTO & TRUCK ACCESSORIES |
| NAICS |
n/a
|
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $5 M to 10M |
| # of Employees | 280 |
| Plant Area |
n/a
|
| Annual Production | 50,000
pieces
|
| Production Hrs. Annual | 2,184
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $55,432 | 863,716 |
kWh
|
$0.064 |
| Natural Gas | $54,233 | 10,972 |
MMBtu
|
$4.94 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $27,852 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $17,933 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.6214: Shut off pilots in standby equipment | $179 | - | - |
$259
-
MMBtu
|
$(-80.0) | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $179 | $200 |
$179
2,931
kWh
|
- | - | |
| 03 | 2.5194: Redesign process | $593 | $200 | - |
$593
-
MMBtu
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,393 | $200 |
$1,393
21,688
kWh
|
- | - | |
| 05 | 2.7243: Improve air circulation with destratification fans / other methods | $1,607 | $5,000 |
$(-493.0)
(-7,620)
kWh
|
$2,100
-
MMBtu
|
- | |
| 06 | 2.3191: Use demand controller or load shedder | $2,309 | $2,400 |
$2,309
-
kWh
|
- | - | |
| 07 | 2.2443: Re-use or recycle hot or cold process exhaust air | $3,744 | $10,000 | - |
$3,744
-
MMBtu
|
- | |
| 08 | 2.7226: Use computer programs to optimize hvac performance | $8,457 | $1,000 |
$222
9,965
kWh
|
$8,235
-
MMBtu
|
- | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,330 | $2,816 |
$1,330
17,585
kWh
|
- | - | |
| 10 | 2.7492: Use proper thickness of insulation on building envelope | $669 | $932 | - |
$669
-
MMBtu
|
- | |
| 11 | 2.7441: Replace broken windows and/or window sash | $6,642 | $390 | - |
$6,642
-
MMBtu
|
- | |
| 12 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $750 | $340 |
$750
11,723
kWh
|
- | - | |
| TOTAL RECOMMENDED | $27,852 | $23,478 |
$5,690
56,272
kWh
|
$22,242
-
MMBtu
|
$(-80.0) | ||
| TOTAL IMPLEMENTED | $17,933 | $2,722 |
$1,615
31,653
kWh
|
$16,398
-
MMBtu
|
$(-80.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs