| Assessment Year | 1984 |
|---|---|
| Principal Product | NEWSPAPER & CIRCULARS |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $10 M to 50M |
| # of Employees | 240 |
| Plant Area |
n/a
|
| Annual Production | 10,800,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $98,600 | 1,677,022 |
kWh
|
$0.059 |
| Natural Gas | $11,182 | 2,118 |
MMBtu
|
$5.28 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $12,088 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,543 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,790 | $1,860 |
$3,790
65,358
kWh
|
- | |
| 02 | 2.2511: Insulate bare equipment | $206 | $320 | - |
$206
-
MMBtu
|
|
| 03 | 2.4221: Install compressor air intakes in coolest locations | $362 | $380 |
$362
6,155
kWh
|
- | |
| 04 | 2.3512: De-energize excess transformer capacity | $772 | $240 |
$772
13,189
kWh
|
- | |
| 05 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $5,990 | - |
$5,990
-
kWh
|
- | |
| 07 | 2.7229: Air condition only space necessary | $183 | $350 |
$183
3,224
kWh
|
- | |
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $785 | $45 |
$143
2,345
kWh
|
$642
-
MMBtu
|
|
| TOTAL RECOMMENDED | $12,088 | $3,195 |
$11,240
90,271
kWh
|
$848
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $11,543 | $2,465 |
$10,695
80,892
kWh
|
$848
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs