| Assessment Year | 2026 |
|---|---|
| Principal Product | Office Building |
| NAICS | 524210: Insurance Agencies and Brokerages |
| SIC | 6411: Insurance Agents, Brokers, and Service |
| Sales Range | $1 M to 5M |
| # of Employees | 50 |
| Plant Area |
20,228
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $27,756 | 130,345 |
kWh
|
$0.21 |
| Electricity Demand | $11,030 | 1,406 |
kW-mo/yr
|
$7.84 |
| Electricity Fees | $3,072 | - |
|
- |
| TOTAL YEARLY COSTS | $41,858 | |||
| RECOMMENDED SAVINGS* | $31,167 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6231: Utilize controls to operate equipment only when needed | $7,623 | $1,600 |
$7,153
33,600
kWh
|
$470
-
kW-mo/yr
|
- | - | |
| 02 | 2.7134: Use photocell controls | $6,119 | $2,700 |
$5,402
19,008
kWh
|
$146
-
kW-mo/yr
|
$296 | $275 | |
| 03 | 2.7262: Separate controls of air handlers from ac/ heating systems | $4,977 | $3,000 |
$4,977
23,377
kWh
|
- | - | - | |
| 04 | 2.3141: Use battery storage for demand control | $3,674 | $44,990 |
$1,469
6,902
kWh
|
$2,205
-
kW-mo/yr
|
- | - | |
| 05 | 2.7493: Use double or triple glazed windows to maintain higher relative humidity and to reduce heat losses | $3,330 | $37,594 |
$3,330
15,641
kWh
|
- | - | - | |
| 06 | 2.7226: Use computer programs to optimize hvac performance | $2,775 | - |
$2,775
13,035
kWh
|
- | - | - | |
| 07 | 2.7232: Replace existing hvac unit with high efficiency model | $2,669 | $40,600 |
$2,669
12,535
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $31,167 | $130,484 |
$27,775
124,098
kWh
|
$2,821
-
kW-mo/yr
|
$296 | $275 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs