Assessment Year | 2017 |
---|---|
Principal Product | Window Frames/Door Frames/Molding |
NAICS | 321911: Wood Window and Door Manufacturing |
SIC | 2431: Millwork |
Sales Range | $50 M to 100M |
# of Employees | 430 |
Plant Area |
500,000
ft2
|
Annual Production | 34,000,000
thousand feet
|
Production Hrs. Annual | 7,464
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,070,790 | 22,707,155 |
kWh
|
$0.047 |
Electricity Demand | $317,034 | 48,269 |
kW-mo/yr
|
$6.57 |
Electricity Fees | $4,460 | - |
|
- |
Natural Gas | $177,296 | 28,715 |
MMBtu
|
$6.17 |
TOTAL YEARLY COSTS | $1,569,580 | |||
RECOMMENDED SAVINGS* | $231,527 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $120,755 | $55,860 |
$120,755
2,561,090
kWh
|
- | - | |
02 | 2.4322: Use or replace with energy efficient substitutes | $55,510 | $60,400 |
$55,510
1,177,310
kWh
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $36,306 | $482 |
$36,306
770,017
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,223 | $948 |
$4,223
89,568
kWh
|
- | - | |
05 | 2.4224: Upgrade controls on compressors | $5,010 | $7,576 |
$3,898
82,668
kWh
|
$1,112
-
kW-mo/yr
|
- | |
06 | 3.1161: Eliminate/reduce an operation | $72 | $169 |
$72
1,519
kWh
|
- | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $444 | $990 |
$444
9,423
kWh
|
- | - | |
08 | 2.6231: Utilize controls to operate equipment only when needed | $2,363 | $968 |
$2,363
50,113
kWh
|
- | - | |
09 | 2.7135: Install occupancy sensors | $338 | $198 |
$338
7,166
kWh
|
- | - | |
10 | 2.7243: Improve air circulation with destratification fans / other methods | $6,506 | $20,241 |
$(-323.0)
(-6,841)
kWh
|
- |
$6,829
-
MMBtu
|
|
TOTAL RECOMMENDED | $231,527 | $147,832 |
$223,586
4,742,033
kWh
|
$1,112
-
kW-mo/yr
|
$6,829
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs