Assessment Year | 2014 |
---|---|
Principal Product | Exterior Signs |
NAICS | 332323: Ornamental and Architectural Metal Work Manufacturing |
SIC | 3993: Signs and Advertising Specialties |
Sales Range | $5 M to 10M |
# of Employees | 91 |
Plant Area |
60,000
ft2
|
Annual Production | 4,000
pieces
|
Production Hrs. Annual | 2,016
hrs
|
Location (State) | Idaho |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $30,224 | 584,480 |
kWh
|
$0.052 |
Electricity Demand | $13,860 | 2,463 |
kW-mo/yr
|
$5.63 |
Electricity Fees | $195 | - |
|
- |
Natural Gas | $41,495 | 5,828 |
MMBtu
|
$7.12 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $28,831 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,058 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $65 | $132 |
$65
1,270
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,413 | $8,156 |
$5,413
104,682
kWh
|
- | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $89 | $113 |
$58
1,130
kWh
|
$30
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $374 | $15 |
$249
4,816
kWh
|
$125
-
kW-mo/yr
|
- | |
05 | 2.7243: Improve air circulation with destratification fans / other methods | $6,366 | $24,165 | - | - |
$6,366
-
MMBtu
|
|
06 | 2.7224: Reduce space conditioning during non-working hours | $8,299 | $50 | - | - |
$8,299
-
MMBtu
|
|
07 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $7,773 | $13,800 | - | - |
$7,773
-
MMBtu
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $452 | $340 | - | - |
$452
-
MMBtu
|
|
TOTAL RECOMMENDED | $28,831 | $46,771 |
$5,785
111,898
kWh
|
$155
-
kW-mo/yr
|
$22,890
-
MMBtu
|
||
TOTAL IMPLEMENTED | $21,058 | $32,971 |
$5,785
111,898
kWh
|
$155
-
kW-mo/yr
|
$15,117
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs