Assessment Year | 2016 |
---|---|
Principal Product | Irrigation Control Equipment |
NAICS | 335314: Relay and Industrial Control Manufacturing |
SIC | 3625: Relays and Industrial Controls |
Sales Range | $5 M to 10M |
# of Employees | 45 |
Plant Area |
94,250
ft2
|
Annual Production | 500,000
units
|
Production Hrs. Annual | 7,332
hrs
|
Location (State) | Illinois |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $99,226 | 1,832,835 |
kWh
|
$0.054 |
Electricity Demand | $35,560 | 5,523 |
kW-mo/yr
|
$6.44 |
Electricity Fees | $2,149 | - |
|
- |
Natural Gas | $28,707 | 3,716 |
MMBtu
|
$7.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $28,019 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2511: Insulate bare equipment | $7,762 | $1,810 |
$6,312
116,466
kWh
|
$1,450
-
kW-mo/yr
|
- | - | - | |
02 | 2.7231: Use radiant heater for spot heating | $4,162 | $8,800 | - | - |
$4,162
-
MMBtu
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,053 | $10,965 |
$3,034
56,074
kWh
|
$2,006
-
kW-mo/yr
|
- | $51 | $(-1,038.0) | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,476 | $15 |
$2,909
53,777
kWh
|
$567
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,361 | $9,836 |
$1,693
31,295
kWh
|
$1,120
-
kW-mo/yr
|
- | $164 | $(-616.0) | |
06 | 2.4221: Install compressor air intakes in coolest locations | $2,961 | $1,500 |
$2,478
45,809
kWh
|
$483
-
kW-mo/yr
|
- | - | - | |
07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,172 | $576 | - | - |
$1,172
-
MMBtu
|
- | - | |
08 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,074 | $50 | - |
$1,074
-
kW-mo/yr
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $469 | $600 |
$205
3,784
kWh
|
$264
-
kW-mo/yr
|
- | - | - | |
10 | 2.4133: Use most efficient type of electric motors | $286 | $320 |
$206
3,805
kWh
|
$80
-
kW-mo/yr
|
- | - | - | |
11 | 2.7135: Install occupancy sensors | $243 | $600 |
$106
1,968
kWh
|
$137
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $28,019 | $35,072 |
$16,943
312,978
kWh
|
$7,181
-
kW-mo/yr
|
$5,334
-
MMBtu
|
$215 | $(-1,654.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs