Assessment Year | 2024 |
---|---|
Principal Product | Meters and controllers |
NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
SIC | 3824: Totalizing Fluid Meters and Counting Devices |
Sales Range | less than $500 k |
# of Employees | 200 |
Plant Area |
19,050
ft2
|
Annual Production | 45,000
units
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $97,843 | 1,202,225 |
kWh
|
$0.081 |
Electricity Fees | $11,301 | - |
|
- |
Natural Gas | $998 | 56 |
MMBtu
|
$17.82 |
TOTAL YEARLY COSTS | $110,142 | |||
RECOMMENDED SAVINGS* | $68,266 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $60,014 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.651: Install back-up equipment | $53,208 | $12,653 | - |
$(-125.0)
-
MMBtu
|
- | $(-1,667.0) | $55,000 | |
02 | 2.6231: Utilize controls to operate equipment only when needed | $7,721 | $37,385 |
$7,721
94,847
kWh
|
- | - | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $3,426 | $278 |
$3,426
42,083
kWh
|
- | - | - | - | |
04 | 2.7226: Use computer programs to optimize hvac performance | $1,801 | $1,399 |
$1,801
22,131
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,321 | $1,387 |
$525
6,443
kWh
|
- | $796 | - | - | |
06 | 2.7135: Install occupancy sensors | $531 | $130 |
$531
6,539
kWh
|
- | - | - | - | |
07 | 2.7132: Install timers on light switches in little used areas | $258 | $79 |
$258
3,168
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $68,266 | $53,311 |
$14,262
175,211
kWh
|
$(-125.0)
-
MMBtu
|
$796 | $(-1,667.0) | $55,000 | ||
TOTAL IMPLEMENTED | $60,014 | $15,796 |
$6,010
73,825
kWh
|
$(-125.0)
-
MMBtu
|
$796 | $(-1,667.0) | $55,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs