Assessment Year | 2021 |
---|---|
Principal Product | Door Hardware |
NAICS | 332510: Hardware Manufacturing |
SIC | 3429: Hardware, Not Elsewhere Classified |
Sales Range | less than $500 k |
# of Employees | 130 |
Plant Area |
134,000
ft2
|
Annual Production | 750,000
units
|
Production Hrs. Annual | 2,567
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $208,524 | 2,774,160 |
kWh
|
$0.075 | |
Electricity Demand | $33,563 | 6,696 |
kW-mo/yr
|
$5.01 | |
Electricity Fees | $8,001 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $19,288 | 2,825 |
Tgal
|
$6.83 | |
Water Disposal | $7,091 | 2,599 |
Tgal
|
$2.73 | |
TOTAL YEARLY COSTS | $276,467 | ||||
RECOMMENDED SAVINGS* | $64,463 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $14,691 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $18,281 | $200 |
$22,457
-
kWh
|
$(-4,721.0)
-
kW-mo/yr
|
$545 | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,025 | $18,448 |
$11,167
148,891
kWh
|
$2,644
-
kW-mo/yr
|
- | - | $214 | |
03 | 2.7144: Install spectral reflectors / delamp | $13,978 | $9,244 |
$13,380
178,397
kWh
|
$263
-
kW-mo/yr
|
- | - | $335 | |
04 | 3.5316: Contract a wood pallet recycling company | $7,800 | $453 | - | - | - | $7,800 | - | |
05 | 2.7272: Install heat pipes / raise cooling setpoint | $6,879 | $560 |
$5,677
75,496
kWh
|
$1,202
-
kW-mo/yr
|
- | - | - | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,097 | $447 |
$146
1,946
kWh
|
$1,951
-
kW-mo/yr
|
- | - | - | |
07 | 2.4224: Upgrade controls on compressors | $713 | $3,359 |
$653
8,713
kWh
|
$60
-
kW-mo/yr
|
- | - | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $690 | $40 |
$632
8,423
kWh
|
$58
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $64,463 | $32,751 |
$54,112
421,866
kWh
|
$1,457
-
kW-mo/yr
|
$545 | $7,800 | $549 | ||
TOTAL IMPLEMENTED | $14,691 | $12,603 |
$14,033
187,110
kWh
|
$323
-
kW-mo/yr
|
- | - | $335 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs