Assessment Year | 1992 |
---|---|
Principal Product | ELECTRONIC SYSTEMS |
NAICS |
n/a
|
SIC | 3678: Electronic Connectors |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 47,000
pieces
|
Production Hrs. Annual | 4,368
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $405,369 | 5,463,951 |
kWh
|
$0.074 |
Natural Gas | $9,207 | 2,004 |
MMBtu
|
$4.59 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $103,224 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $63,926 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,582 | $57,505 |
$20,298
172,040
kWh
|
$(-3,716.0) | |
02 | 2.7123: Keep lamps and reflectors clean | $41,506 | $83,545 |
$41,506
559,496
kWh
|
- | |
03 | 2.6232: Install set-back timers | $890 | $1,500 |
$890
12,016
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $454 | $700 |
$454
6,155
kWh
|
- | |
05 | 2.4133: Use most efficient type of electric motors | $491 | $3,390 |
$491
6,741
kWh
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,522 | - |
$1,522
20,516
kWh
|
- | |
07 | 2.4322: Use or replace with energy efficient substitutes | $1,767 | $69,018 |
$1,767
23,740
kWh
|
- | |
08 | 2.7252: Utilize an evaporative air pre-cooler or other heat exchanger in ac system | $2,191 | $5,600 |
$2,191
29,601
kWh
|
- | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,248 | $500 |
$1,248
16,706
kWh
|
- | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,233 | $100 |
$1,233
16,706
kWh
|
- | |
11 | 2.8114: Change rate schedules or other changes in utility service | $35,340 | $50,250 |
$35,340
-
kWh
|
- | |
TOTAL RECOMMENDED | $103,224 | $272,108 |
$106,940
863,717
kWh
|
$(-3,716.0) | ||
TOTAL IMPLEMENTED | $63,926 | $147,240 |
$67,642
810,376
kWh
|
$(-3,716.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs