Assessment Year | 2023 |
---|---|
Principal Product | Threaded pipe joints |
NAICS | 332996: Fabricated Pipe and Pipe Fitting Manufacturing |
SIC | 3498: Fabricated Pipe and Pipe Fittings |
Sales Range | $5 M to 10M |
# of Employees | 40 |
Plant Area |
56,975
ft2
|
Annual Production | 135,000
pieces
|
Production Hrs. Annual | 3,064
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $39,265 | 572,014 |
kWh
|
$0.069 |
Electricity Demand | $33,045 | 4,210 |
kW-mo/yr
|
$7.85 |
Electricity Fees | $6,715 | - |
|
- |
TOTAL YEARLY COSTS | $79,025 | |||
RECOMMENDED SAVINGS* | $49,040 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $30,265 | $6,430 | - | - | $6,065 | - | - | $24,200 | |
02 | 2.3212: Optimize plant power factor | $5,195 | $11,085 | - |
$5,195
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,050 | $8,145 |
$2,430
35,200
kWh
|
$1,340
-
kW-mo/yr
|
- | - | $280 | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $3,790 | $825 |
$3,790
54,900
kWh
|
- | - | - | - | - | |
05 | 2.6218: Turn off equipment when not in use | $955 | - |
$3,140
45,515
kWh
|
- | - | $(-2,185.0) | - | - | |
06 | 2.7132: Install timers on light switches in little used areas | $1,995 | $257 |
$1,995
28,885
kWh
|
- | - | - | - | - | |
07 | 2.4157: Establish a predictive maintenance program | $1,765 | $4,340 |
$375
5,475
kWh
|
$265
-
kW-mo/yr
|
- | $1,125 | - | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $485 | $200 |
$310
4,460
kWh
|
$175
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.8123: Pay utility bills on time | $275 | - | - | - | $275 | - | - | - | |
10 | 2.7124: Make a practice of turning off lights when not needed | $265 | $320 |
$165
2,400
kWh
|
$100
-
kW-mo/yr
|
- | - | - | - | |
TOTAL RECOMMENDED | $49,040 | $31,602 |
$12,205
176,835
kWh
|
$7,075
-
kW-mo/yr
|
$6,340 | $(-1,060.0) | $280 | $24,200 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs