ITAC Assessment: WV0700
ITAC logo
ITAC Assessment: WV0700
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2026
Principal Product Power Distribution Components
NAICS 335311: Power, Distribution, and Specialty Transformer Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range $50
M
to 100
M
# of Employees 450
Plant Area 180,000
ft2
Annual Production 100,000
units
Production Hrs. Annual 7,904
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $240,256 2,857,351
kWh
Electricity Demand $46,823 6,011
kW-mo/yr
Natural Gas $69,630 10,722
MMBtu
TOTAL YEARLY COSTS $356,709
RECOMMENDED SAVINGS* $47,872 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $22,299 $86,100 $19,549
232,444
kWh
$2,750
-
kW-mo/yr
02 2.3131: Reschedule plant operations or reduce load to avoid peaks $6,816 $7,000 - $6,816
-
kW-mo/yr
03 2.7135: Install occupancy sensors $6,781 $4,160 $5,947
70,716
kWh
$834
-
kW-mo/yr
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,922 $441 $4,314
51,299
kWh
$608
-
kW-mo/yr
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $3,297 $700 $2,892
34,388
kWh
$405
-
kW-mo/yr
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,452 $3,984 $1,273
15,141
kWh
$179
-
kW-mo/yr
07 2.4224: Upgrade controls on compressors $1,012 $3,260 $835
9,930
kWh
$177
-
kW-mo/yr
08 2.4239: Eliminate or reduce compressed air usage $797 $1,958 $696
8,281
kWh
$101
-
kW-mo/yr
09 2.4231: Reduce the pressure of compressed air to the minimum required $496 $600 $434
5,162
kWh
$62
-
kW-mo/yr
TOTAL RECOMMENDED $47,872 $108,203 $35,940
427,361
kWh
$11,932
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs