Assessment Year 2022
Principal Product Medium Duty Truck
NAICS 336120: Heavy Duty Truck Manufacturing
SIC 3713: Truck and Bus Bodies
Sales Range $50
M
to 100
M
# of Employees 375
Plant Area 970,000
ft2
Annual Production 13,500
units
Production Hrs. Annual 2,250
hrs
Location (State) West Virginia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $154,857 3,822,182
kWh
Electricity Demand $163,386 10,308
kW-mo/yr
Natural Gas $58,492 8,332
MMBtu
Waste Disposal Costs
Water Usage $2,659 444,645
Tgal
Water Disposal $3,001 444,645
Tgal
Other Liquid (non-haz) $15,321 14,056
gal
TOTAL YEARLY COSTS $397,716
RECOMMENDED SAVINGS* $53,983 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $12,412

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings Personnel Changes Savings Ancillary Material Cost Savings
01 2.7447: Install vinyl strip / high speed / air curtain doors $13,903 $67,984 $739
18,252
kWh
$507
-
kW-mo/yr
$12,657
-
MMBtu
- - -
02 3.3131: Use evaporation to concentrate material $9,086 $4,900 $(-1,068.0)
(-26,370)
kWh
$(-571.0)
-
kW-mo/yr
- $10,725
-
gal
- -
03 2.7313: Recycle air for heating, ventilation and air conditioning $7,597 $37,000 $1,406
34,706
kWh
$2,932
-
kW-mo/yr
$7,259
-
MMBtu
- $(-4,000.0) -
04 2.4231: Reduce the pressure of compressed air to the minimum required $6,233 $660 $2,017
49,803
kWh
$4,216
-
kW-mo/yr
- - - -
05 2.7245: Use direct air supply to exhaust hoods $4,159 $8,300 $582
14,365
kWh
$1,696
-
kW-mo/yr
$1,881
-
MMBtu
- - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $3,394 $7,905 $1,354
33,439
kWh
$2,790
-
kW-mo/yr
- - $(-750.0) -
07 2.3212: Optimize plant power factor $2,785 $7,090 - - - - - $2,785
08 2.4224: Upgrade controls on compressors $2,669 $3,970 $1,449
35,784
kWh
$1,220
-
kW-mo/yr
- - - -
09 2.4221: Install compressor air intakes in coolest locations $2,129 $1,773 $687
16,952
kWh
$1,442
-
kW-mo/yr
- - - -
10 2.1321: Replace fossil fuel equipment with electrical equipment $2,028 $9,280 $(-1,185.0)
(-29,250)
kWh
$(-2,473.0)
-
kW-mo/yr
$5,686
-
MMBtu
- - -
TOTAL RECOMMENDED $53,983 $148,862 $5,981
147,681
kWh
$11,759
-
kW-mo/yr
$27,483
-
MMBtu
$10,725
-
gal
$(-4,750.0) $2,785
TOTAL IMPLEMENTED $12,412 $15,655 $3,371
83,242
kWh
$7,006
-
kW-mo/yr
- - $(-750.0) $2,785
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (non-haz) Savings Personnel Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs