ITAC Assessment: WV0393
ITAC logo
ITAC Assessment: WV0393
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2009
Principal Product Drapery Hardware & Blinds & Shades
NAICS 314120: Curtain and Linen Mills
SIC 2591: Drapery Hardware and Window Blinds and Shades
Sales Range $50
M
to 100
M
# of Employees 532
Plant Area 380,000
ft2
Annual Production 1,000,000
units
Production Hrs. Annual 4,680
hrs
Location (State) Maryland

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $324,245 3,678,654
kWh
Electricity Demand $97,825 9,076
kW-mo/yr
Electricity Fees $1,647 -
Natural Gas $60,260 4,569
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $144,050 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $83,421

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $69,642 $143,500 $59,010
669,500
kWh
$10,632
-
kW-mo/yr
- - - -
02 2.7241: Install outside air damper / economizer on hvac unit $45,591 $127,000 $53,742
609,733
kWh
$16,849
-
kW-mo/yr
- $(-25,000.0) - -
03 2.8114: Change rate schedules or other changes in utility service $8,129 $2,000 - - - - $8,129 -
04 2.2628: Utilize a less expensive cooling method $5,419 $4,400 $3,091
36,416
kWh
$2,328
-
kW-mo/yr
- - - -
05 2.3191: Use demand controller or load shedder $4,441 $7,800 - $4,441
-
kW-mo/yr
- - - -
06 2.2437: Recover waste heat from equipment $2,691 $2,450 - - $2,691
-
MMBtu
- - -
07 2.2443: Re-use or recycle hot or cold process exhaust air $2,298 $3,800 - - $3,298
-
MMBtu
- - $(-1,000.0)
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,009 $500 $1,529
17,352
kWh
$480
-
kW-mo/yr
- - - -
09 2.4239: Eliminate or reduce compressed air usage $1,723 $2,067 $1,313
14,892
kWh
$410
-
kW-mo/yr
- - - -
10 2.4221: Install compressor air intakes in coolest locations $764 $220 $581
6,587
kWh
$183
-
kW-mo/yr
- - - -
11 2.7447: Install vinyl strip / high speed / air curtain doors $554 $56 - - $554
-
MMBtu
- - -
12 2.4231: Reduce the pressure of compressed air to the minimum required $419 $20 $322
3,654
kWh
$97
-
kW-mo/yr
- - - -
13 2.4111: Utilize energy-efficient belts and other improved mechanisms $370 - $228
5,153
kWh
$142
-
kW-mo/yr
- - - -
TOTAL RECOMMENDED $144,050 $293,813 $119,816
1,363,287
kWh
$35,562
-
kW-mo/yr
$6,543
-
MMBtu
$(-25,000.0) $8,129 $(-1,000.0)
TOTAL IMPLEMENTED $83,421 $149,876 $61,089
695,659
kWh
$11,351
-
kW-mo/yr
$3,852
-
MMBtu
- $8,129 $(-1,000.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs