| Assessment Year | 2008 |
|---|---|
| Principal Product | Newspaper |
| NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
| SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 415 |
| Plant Area |
175,000
ft2
|
| Annual Production | 310
ton
|
| Production Hrs. Annual | 6,570
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $209,285 | 7,323,380 |
kWh
|
$0.029 |
| Electricity Demand | $202,279 | 17,683 |
kW-mo/yr
|
$11.44 |
| Natural Gas | $67,019 | 5,610 |
MMBtu
|
$11.95 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $36,011 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $10,036 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7314: Reduce ventilation air | $13,257 | $5,000 |
$486
16,994
kWh
|
$355
-
kW-mo/yr
|
$12,416
-
MMBtu
|
- | |
| 02 | 2.4224: Upgrade controls on compressors | $5,179 | $7,500 |
$2,994
104,763
kWh
|
$2,185
-
kW-mo/yr
|
- | - | |
| 03 | 2.1224: Replace boiler | $4,983 | $9,450 | - | - |
$4,983
-
MMBtu
|
- | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,055 | $50 |
$1,762
61,640
kWh
|
$1,293
-
kW-mo/yr
|
- | - | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $2,337 | $1,049 |
$1,227
42,947
kWh
|
$1,110
-
kW-mo/yr
|
- | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,268 | $260 |
$1,307
45,728
kWh
|
$961
-
kW-mo/yr
|
- | - | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $1,141 | $200 |
$659
23,051
kWh
|
$482
-
kW-mo/yr
|
- | - | |
| 08 | 2.7135: Install occupancy sensors | $1,008 | $375 |
$585
20,486
kWh
|
$423
-
kW-mo/yr
|
- | - | |
| 09 | 2.2414: Use waste heat from hot flue gases to preheat | $1,006 | $2,125 | - | - |
$1,006
-
MMBtu
|
- | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $742 | $1,995 |
$387
13,544
kWh
|
$355
-
kW-mo/yr
|
- | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $655 | - |
$380
13,262
kWh
|
$275
-
kW-mo/yr
|
- | - | |
| 12 | 2.1233: Analyze flue gas for proper air/fuel ratio | $380 | $800 | - | - |
$418
-
MMBtu
|
$(-38.0) | |
| TOTAL RECOMMENDED | $36,011 | $28,804 |
$9,787
342,415
kWh
|
$7,439
-
kW-mo/yr
|
$18,823
-
MMBtu
|
$(-38.0) | ||
| TOTAL IMPLEMENTED | $10,036 | $12,880 |
$2,659
93,020
kWh
|
$2,014
-
kW-mo/yr
|
$5,401
-
MMBtu
|
$(-38.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs