Assessment Year 2008
Principal Product Lumber
NAICS 321113: Sawmills
SIC 2421: Sawmills and Planing Mills, General
Sales Range $10
M
to 50
M
# of Employees 175
Plant Area 40,000
ft2
Annual Production 18,000,000
units
Production Hrs. Annual 2,678
hrs
Location (State) West Virginia

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $369,024 12,451,472
kWh
Electricity Demand $265,701 30,526
kW-mo/yr
Electricity Fees $406 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $913,782 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $39,792

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Wood Savings Other Energy Savings Personnel Changes Savings
01 2.3414: Burn waste to produce steam to drive a steam turbine generator set and use steam exhaust for heat $870,056 $3,850,000 $201,660
6,812,832
kWh
$168,815
-
kW-mo/yr
$(-55,488.0)
-
MMBtu
$555,069
-
MMBtu
-
02 2.4157: Establish a predictive maintenance program $16,386 $3,500 $7,553
255,180
kWh
$9,948
-
kW-mo/yr
- - $(-1,115.0)
03 2.4151: Develop a repair/replace policy $11,577 $1,336 $5,035
170,114
kWh
$6,632
-
kW-mo/yr
- - $(-90.0)
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $9,511 - $4,104
138,589
kWh
$5,407
-
kW-mo/yr
- - -
05 2.2437: Recover waste heat from equipment $2,892 $485 $1,248
42,179
kWh
$1,644
-
kW-mo/yr
- - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,538 - $981
33,138
kWh
$557
-
kW-mo/yr
- - -
07 2.4221: Install compressor air intakes in coolest locations $1,042 $185 $554
18,713
kWh
$488
-
kW-mo/yr
- - -
08 2.4231: Reduce the pressure of compressed air to the minimum required $780 $2,158 $336
11,352
kWh
$444
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $913,782 $3,857,664 $221,471
7,482,097
kWh
$193,935
-
kW-mo/yr
$(-55,488.0)
-
MMBtu
$555,069
-
MMBtu
$(-1,205.0)
TOTAL IMPLEMENTED $39,792 $6,994 $18,009
608,373
kWh
$22,988
-
kW-mo/yr
- - $(-1,205.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Wood Savings Other Energy Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs