Assessment Year | 2005 |
---|---|
Principal Product | Printing and Cutting of Cardboard Boxes |
NAICS | 312230: Tobacco Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 200 |
Plant Area |
120,000
ft2
|
Annual Production | 50,000,000
pieces
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $214,568 | 9,720,000 |
kWh
|
$0.022 |
Electricity Demand | $136,367 | 16,529 |
kW-mo/yr
|
$8.25 |
Electricity Fees | $7,892 | - |
|
- |
Natural Gas | $628,227 | 66,629 |
MMBtu
|
$9.43 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $71,689 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,037 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $15,023 | $6,435 | - | - |
$15,023
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,049 | $18,750 |
$8,810
384,573
kWh
|
$5,239
-
kW-mo/yr
|
- | - | |
03 | 2.4323: Use optimum size and capacity equipment | $14,013 | $9,600 |
$9,314
406,690
kWh
|
$4,699
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,107 | $2,970 |
$4,059
177,265
kWh
|
$2,048
-
kW-mo/yr
|
- | - | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $5,641 | $7,480 |
$3,834
167,408
kWh
|
$1,807
-
kW-mo/yr
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,708 | $250 |
$3,129
136,639
kWh
|
$1,579
-
kW-mo/yr
|
- | - | |
07 | 2.4151: Develop a repair/replace policy | $3,672 | $413 |
$2,919
127,455
kWh
|
$1,473
-
kW-mo/yr
|
- | $(-720.0) | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,210 | $4,800 |
$1,476
63,872
kWh
|
$734
-
kW-mo/yr
|
- | - | |
09 | 2.7135: Install occupancy sensors | $1,797 | $2,788 |
$1,181
51,568
kWh
|
$616
-
kW-mo/yr
|
- | - | |
10 | 2.2628: Utilize a less expensive cooling method | $1,712 | $824 |
$1,138
49,707
kWh
|
$574
-
kW-mo/yr
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,460 | - |
$973
42,336
kWh
|
$487
-
kW-mo/yr
|
- | - | |
12 | 2.7111: Reduce illumination to minimum necessary levels | $706 | $120 |
$450
19,591
kWh
|
$256
-
kW-mo/yr
|
- | - | |
13 | 2.4322: Use or replace with energy efficient substitutes | $591 | $130 |
$393
17,141
kWh
|
$198
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $71,689 | $54,560 |
$37,676
1,644,245
kWh
|
$19,710
-
kW-mo/yr
|
$15,023
-
MMBtu
|
$(-720.0) | ||
TOTAL IMPLEMENTED | $31,037 | $29,678 |
$20,078
875,844
kWh
|
$10,959
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs